If caliber of the communication cord is too large, which causes difficulty in leading or sticking the cord according to
above point 2 and point 5, strip some of the sheath of the communication cable to meet the installation requirement.
2.2.3 Removal method
Fig.2.1.3 Removal of Wired Controller
2.2.4 Connection of communication cord
There are 4 ways to connect
wired controller with indoor units’ network:
Fig. 2.2.4.1 One wired controller Fig. 2.2.4.2 Two wired controllers