GREE DC Inverter Side Discharge VRF
Ⅱ
for North America
94
No.
Debug item
Parameter
name
Unit
Reference
12
GMV-60WL/A-T(U)
GMV-60WL/C-T(U)
Changes in
0~40Hz according
to system’s
pressure.
13
IDU
paramet
ers
IDU ambient
temp
℃
(
℉
)
-
14
Indoor heat
exchanger’s
inlet temp
℃
(
℉
)
According to ambient temp, for a same IDU in cool mode,
the inlet temp will be 1
℃
~7
℃
(34~45
℉
) lower than the outlet
temp, and 4~9
℃
(39~48
℉
) higher than the low pressure
value.
For a same IDU in heat mode, the inlet temp will be 10
℃
~20
℃
(50~68
℉
) lower than the outlet temp.
15
Opening angle
of indoor EXV
PLS
GMV-24WL/C-T(U)
GMV-28WL/C-T(U)
In cool mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
In heat mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
16
GMV-36WL/A-T(U)
GMV-48WL/A-T(U)
GMV-36WL/C-T(U)
GMV-48WL/C-T(U)
In cool mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
In heat mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
17
GMV-60WL/A-T(U)
GMV-60WL/C-T(U)
In cool mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
In heat mode, the
opening angle of
indoor EXV varies
within 40~480PLS.
18
Communication
parameters
Communicatio
n data
-
Number of IDUs detected by software is the same with the
actual number. No communication error.
19
Drainage system
-
-
Indoor unit can drain water out completely and smoothly.
Condensate pipe has no backward slope of water; Water of
outdoor unit can be drained completely through drainage
pipe. No water drop from unit base.
20
Others
-
-
Compressor and indoor/outdoor fan motor do not have
strange noise. Unit can operate normally.
Содержание GMV-24WL/C-T
Страница 1: ...DC Inverter Side Discharge VRF for North America Capacity 24 kBtu h 60 kBtu h Rated Frequency 60 Hz...
Страница 4: ...GREE DC Inverter Side Discharge VRF for North America 1 PRODUCT...
Страница 12: ...GREE DC Inverter Side Discharge VRF for North America 9 CONTROL...
Страница 17: ...GREE DC Inverter Side Discharge VRF for North America 14...
Страница 18: ...GREE DC Inverter Side Discharge VRF for North America 15 Button Graphics...
Страница 65: ...GREE DC Inverter Side Discharge VRF for North America 62 Switchover of Software Languages...
Страница 66: ...GREE DC Inverter Side Discharge VRF for North America 63 INSTALLATION...
Страница 98: ...GREE DC Inverter Side Discharge VRF for North America 95 MAINTENANCE...
Страница 115: ...GREE DC Inverter Side Discharge VRF for North America 112 GMV 36WL A T U GMV 48WL A T U GMV 36WL C T U GMV 48WL C T U...
Страница 116: ...GREE DC Inverter Side Discharge VRF for North America 113 GMV 60WL A T U 4 Removal of Parts GMV 60WL C T U...
Страница 150: ...JF00302320...