GREE
GMV5 INDOOR UNIT SERVICE MANUAL
77
Method 2:
Step 1: Press and hold the
“FUNCTION” button for five seconds in power-on or power-off status to
enter the parameter query interface.
Step 2: Press and hold the
“FUNCTION” button for five seconds in “C00” status to enter the
parameter setting interface.
Step 3: Press
“▲” or “▼” to switch level 2 parameter codes till “P10” is displayed on the temperature
area.
Step 4: Press the
“MODE” button to set the parameter to “01” and then Press the “SWING/ENTER”
button. If the setting is successful,
“MASTER” on the wired controller will be on.
Master IDU Display
①
For IDUs connected with wired controllers,
“MASTER” on the wired controller connected with
the master IDU will be on.
②
For IDUs embedded or connected with LED panels, the operation LED on the LED panel of the
master IDU will blink three times.
Note:
After the master IDU is successfully set, stick the
“
” flag to the wired controller or unit panel
for convenience of user operation and engineering maintenance. This flag is placed in the package bag
of the ODU.
MASTER
Содержание CM100N1320
Страница 1: ...Multi Variable Air Conditioners Indoor Units GC201809 VI...
Страница 6: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 1 PRODUCT...
Страница 50: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 45 CONTROL...
Страница 51: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 46 1 Operation Flowchart...
Страница 91: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 86 INSTALLATION...
Страница 136: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 131 Maintenance...
Страница 151: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 146 GMV ND160PHS A T GMV ND224PH A T GMV ND280PH A T...
Страница 276: ...JF00302966...