GREE
GMV5 INDOOR UNIT SERVICE MANUAL
43
3.15 AHU-KIT Type
Model
GMV-N36U/A-T
GMV-N71U/A-T
GMV-N140U/A-T
Defaulted capacity of
ex-factory
Capacity
36
71
140
Cooling
kW
3.6
7.1
14.0
Heating
kW
4.0
8.0
16.0
Adjustable capacity
Capacity
28
36
45
56
71
90
112
140
Cooling
kW
2.8
3.6
4.5
5.6
7.1
9.0
11.2
14.0
Heating
kW
3.2
4.0
5.0
6.3
8.0
10.0
12.5
16.0
Power input
W
5.0
5.0
5.0
Power Supply
V/Ph/Hz
220~240/1/50 & 08~230/1/60
Size of
connection
pipe
AHU-KIT
(ex-factory pipe size)
mm
Φ6.35
Φ6.35
Φ9.52
Φ9.52
Φ9.52 Φ9.52 Φ9.52 Φ9.52
Air
handling
unit
Liquid pipe
mm
Φ6.35
Φ6.35
Φ6.35
Φ9.52
Φ9.52 Φ9.52 Φ9.52 Φ9.52
Gas pipe
mm
Φ9.52
Φ12.7
Φ12.7
Φ15.9
Φ15.9 Φ15.9 Φ15.9 Φ15.9
Connection method
Brazing Connection
Brazing Connection
Brazing Connection
Outline dimension
(W×D×H)
EXV box
mm
203×326×85
203×326×85
203×326×85
Control box
mm
334×284×111
334×284×111
334×284×111
Packing size(W×D×H)
mm
539×461×247
539×461×247
539×461×247
Net weight
kg
8.6
8.6
8.6
Model
GMV-N280U/A-T
GMV-N560U/A-T
Defaulted capacity
of ex-factory
Capacity
280
560
Cooling
kW
28.0
56.0
Heating
kW
31.5
63.0
Adjustable capacity
Capacity
224
280
335
400
450
504
560
840
Cooling
kW
22.4
28.0
33.5
40.0
45.0
50.4
56.0
84.0
Heating
kW
25.0
31.50
37.5
45.00
50.00
56.50
63.0
94.5
Power input
W
5.0
5.0
Power Supply
V/Ph/Hz
220~240/1/50 & 208~230/1/60
Size of
connecti
on pipe
AHU-KIT
(ex-factory pipe size)
mm
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Φ15.9 Φ15.9 Φ15.9
Air
handling
unit
Liquid pipe
mm
Φ9.52
Φ9.52
Φ12.7
Φ12.7
Φ12.7
Φ15.9 Φ15.9 Φ19.05
Gas pipe
mm
Φ19.05 Φ22.2
Φ25.4
Φ25.4
Φ28.6
Φ28.6 Φ28.6 Φ31.8
Connection method
Brazing Connection
Brazing Connection
Outline dimension
(W×D×H)
EXV box
mm
203×326×85
246×500×120
Control box
mm
334×284×111
334×284×111
Packing size(W×D×H)
mm
539×461×247
759×645×180
Net weight
kg
8.6
11.8
Model(Combined)
GMV-N560U/A-
T+GMV-N140U/A-T
GMV-N560U/A-
T+GMV-N280U/A-T
GMV-N560U/A-
T+GMV-N560U/A-T
Capacity
840+140
840+280
840+560
840+840
Cooling
kW
98
112
140
168
Heating
kW
110.5
126
157.5
189
Power input
W
5
5
5
Power Supply
V/Ph/Hz
220/1/50
220/1/50
220/1/50
Size of connection
pipe
Air handling
unit
Liquid pipe
Φ19.05
Φ19.05
Φ19.05
Φ19.05
Gas pipe
Φ38.1
Φ38.1
Φ41.3
Φ41.3
Outline dimension
EXV box
mm
246×500×120+203
×326×85
246×500×120+203
×326×85
(246×500×120)×2
Содержание CM100N1320
Страница 1: ...Multi Variable Air Conditioners Indoor Units GC201809 VI...
Страница 6: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 1 PRODUCT...
Страница 50: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 45 CONTROL...
Страница 51: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 46 1 Operation Flowchart...
Страница 91: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 86 INSTALLATION...
Страница 136: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 131 Maintenance...
Страница 151: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 146 GMV ND160PHS A T GMV ND224PH A T GMV ND280PH A T...
Страница 276: ...JF00302966...