GREE
GMV5 INDOOR UNIT SERVICE MANUAL
76
to enter the wired controller engineering parameter setting interface. The temperature area
displays
“P00”.
(2) Select a parameter code by pressing
“
” or “
”. Press the “MODE” button to switch to
parameter value settings. The parameter value blinks. Adjust the parameter value by pressing
“ ” or “ ” and then press the “SWING” button to complete settings.
(3) Press the
“SWING” button to return to the upper-level menu till quitting parameter settings.
For the engineering parameter setting list of the XK49 wired controller, refer to the engineering setting
query list in
XK46 engineering parameter settings
.
Note:
In parameter settings, the function of
“SWING” on the XK49 wired controller is equivalent to the
function of
“ENTER/CANCEL” on the XK46 wired controller.
5.3 Engineering Application Functions Operated through the
XK79 Wired Controller
5.3.1 Master IDU Settings
The master IDU can be set through the wired controller or remote controller. The methods for setting
the master IDU through the wired controller are as follows:
Method 1:
Step 1: Set an IDU to power-off status.
Step 2: Press and hold the
“MODE” button on the wired controller for more than five seconds.
Step 3: Check whether the setting is successful. If it is,
“MASTER” on the wired controller will be on.
Otherwise, repeat steps 1 and 2.
Содержание CM100N1320
Страница 1: ...Multi Variable Air Conditioners Indoor Units GC201809 VI...
Страница 6: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 1 PRODUCT...
Страница 50: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 45 CONTROL...
Страница 51: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 46 1 Operation Flowchart...
Страница 91: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 86 INSTALLATION...
Страница 136: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 131 Maintenance...
Страница 151: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 146 GMV ND160PHS A T GMV ND224PH A T GMV ND280PH A T...
Страница 276: ...JF00302966...