GREE
GMV5 INDOOR UNIT SERVICE MANUAL
74
5.2 Engineering Application Functions Operated through the
XK49 Wired Controller
XK49 Wired Controller
5.2.1 Master IDU Settings
Method 1: In power-off status, press and hold the
“MODE” button for five seconds to set the IDU
connected with the current wired controller to master IDU. If the setting is successful,
“MASTER” will be
on.
Method 2:
Step 1: In power-on or power-off status, press and hold the
“MODE” button and “SWING”
simultaneously for five seconds to enter the parameter query interface.
Step 2: In
“C00” status, press and hold the “MODE” button and “SWING” simultaneously for five
seconds to enter the parameter setting interface.
Step 3: Press
“▲” or “▼” to switch level 2 parameter codes till “P10” is displayed on the temperature
area.
Step 4: Press the
“MODE” button to set the parameter to “01” and then Press the “ENTER” button.
If the setting is successful,
“MASTER” on the wired controller will be on.
GREE
MASTER
SWING
FAN
MODE
5.2.2 User Parameter Query
User parameters can be queried in power-on or power-off status.
“MASTER”
图标
Содержание CM100N1320
Страница 1: ...Multi Variable Air Conditioners Indoor Units GC201809 VI...
Страница 6: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 1 PRODUCT...
Страница 50: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 45 CONTROL...
Страница 51: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 46 1 Operation Flowchart...
Страница 91: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 86 INSTALLATION...
Страница 136: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 131 Maintenance...
Страница 151: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 146 GMV ND160PHS A T GMV ND224PH A T GMV ND280PH A T...
Страница 276: ...JF00302966...