GREE
GMV5 INDOOR UNIT SERVICE MANUAL
16
Model
GMV-
ND80T/A-T
GMV-
ND90T/A-T
GMV-
ND100T/A-T
GMV-
ND112T/A-T
GMV-
ND125T/A-T
GMV-
ND140T/A-T
GMV-
ND160T/A-T
Horse Power
HP
3
4
4
4
5
5
5
Cooling capacity
kW
8.0
9.0
10.0
11.2
12.5
14.0
16.0
Heating capacity
kW
9.0
10.0
11.2
12.5
14.0
16.0
17.5
Air volume
m
3
/h
1180
1500
1500
1700
1860
1860
2100
Cooling power input
W
68
98
98
110
110
110
120
Cooling current input
A
0.3
0.4
0.4
0.5
0.5
0.5
0.6
Heating power input
W
68
98
98
110
110
110
120
Heating current input
A
0.3
0.4
0.4
0.5
0.5
0.5
0.6
*Minimum line current
A
0.38
0.5
0.5
0.63
0.63
0.63
0.75
*Maximum fuse current
A
6
6
6
6
6
6
6
Sound pressure level dB(A)
38
40
40
41
43
43
47
Power supply**
220-240V 1 phase ~50Hz/208-230V 1 phase ~60Hz
Piping
interface
Liquid pipe mm
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Gas pipe
mm
Φ15.9
Φ15.9
Φ15.9
Φ15.9
Φ15.9
Φ15.9
Φ15.9
Drain pipe
External
diameter
×thickness
mm
Φ25×2.5
Φ25×2.5
Φ25×2.5
Φ25×2.5
Φ25×2.5
Φ25×2.5
Φ25×2.5
Main body
dimensions
W×D×H
mm
840×840
×240
840×840
×320
840×840
×320
840×840
×320
840×840
×320
840×840
×320
910×910
×293
Panel
dimensions
W×D×H
mm
950×950
×65
950×950
×65
950×950
×65
950×950
×65
950×950
×65
950×950
×65
1040
×1040×65
Net weight
Main body
kg
26.5
32.5
32.5
32.5
32.5
32.5
46.5
Panel
kg
7
7
7
7
7
7
7.5
Notes:
①
Rated cooling capacity test conditions: indoor 27°C DB/19°C WB, outdoor 35°C DB; connection
pipe length: 5 m, without height drop between units.
②
Rated heating capacity test conditions: indoor 20°C DB, outdoor 7°C DB/6 °C WB; connection
pipe length: 5 m, without height drop between units.
3.5 Compact 4-way Cassette Type
Model
GMV-
ND22T/B-T
GMV-
ND28T/B-T
GMV-
ND36T/B-T
GMV-
ND45T/B-T
GMV-
ND50T/B-T
GMV-
ND56T/B-T
Horse Power
HP
1
1
1.5
2
2
2
Cooling capacity
kW
2.2
2.8
3.6
4.5
5.0
5.6
Heating capacity
kW
2.5
3.2
4.0
5.0
5.6
6.3
Air volume
m
3
/h
600
600
600
700
700
700
Cooling power input
W
35
35
35
45
45
45
Cooling current input
A
0.4
0.4
0.4
0.5
0.5
0.5
Heating power input
W
35
35
35
45
45
45
Содержание CM100N1320
Страница 1: ...Multi Variable Air Conditioners Indoor Units GC201809 VI...
Страница 6: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 1 PRODUCT...
Страница 50: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 45 CONTROL...
Страница 51: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 46 1 Operation Flowchart...
Страница 91: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 86 INSTALLATION...
Страница 136: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 131 Maintenance...
Страница 151: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 146 GMV ND160PHS A T GMV ND224PH A T GMV ND280PH A T...
Страница 276: ...JF00302966...