GREE
GMV5 INDOOR UNIT SERVICE MANUAL
64
settings.
(4) The user parameter setting list is as follows:
Table 2.2 User Parameter Setting List
Parameter
Code
Parameter
Name
Parameter Range
Default
Value
Remark
P10
Master IDU
settings
00: does not change the
master/slave status of
the current IDU
01: sets the current IDU
to master IDU
00
After the IDU connected
with the current wired controller is
successfully set to master IDU,
“MASTER”
on the wired controller is on.
P11
Infrared
connection
settings of
wired controller
00: disabled
01: enabled
01
This setting can only be enabled through
the master wired controller.
When the infrared remote receiving
function of the wired controller is disabled,
neither the master nor slave wired
controller can receive remote signals. The
wired controllers can only be operated by
pressing.
P13
Wired
controller
address
settings
01: master wired
controller
02: slave wired controller
01
When two wired controllers simultaneously
control one or more IDUs, the two wired
controllers should use different addresses.
The slave wired controller (address: 02)
does not have the unit parameter setting
function except its own address settings.
P14
Group-
controlled IDU
quantity
settings
00: disabled
01-16: number of indoor
units
01
This value is set based on the number of
connected IDUs.
If the current value is inconsistent with the
actual number of group-controlled IDUs, an
“L9” fault may occur.
P30
Static pressure
settings for
indoor fan
Type 1: 03.04.05.06.07
Type 2:
01.02.03.04.05.06.07.08
.09
05
After identifying the IDU type, the wired
controller only displays the available static
pressure levels.
1) The static pressure levels fall into five
levels and nine levels for VRF IDUs. The
wired controller only displays the static
pressure levels matched with the identified
IDU type.
2) When the HBS network consists of IDUs
with both five and nine static pressure
levels, the wired controller displays nine
adjustable static pressure levels according
to the maximum control principle. If the
static pressure levels received by the IDU
from the wired controller, remote controller,
or remote monitoring system exceed the
setting range, the limit value prevails.
3)During power-on and synchronization,
the setting value of static pressure levels is
determined by settings of the IDU.
P31
High-ceiling
installation
00: standard-ceiling
installation height
01: high-ceiling
installation height
00
P33
Timer function
settings
00: common timing
01: time-point timing
00
P34
Repeating
validity for
time-point
timing
00: single timing
01: repeated everyday
00
This setting is valid only when the timer
function is set to time-point timing.
Содержание CM100N1320
Страница 1: ...Multi Variable Air Conditioners Indoor Units GC201809 VI...
Страница 6: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 1 PRODUCT...
Страница 50: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 45 CONTROL...
Страница 51: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 46 1 Operation Flowchart...
Страница 91: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 86 INSTALLATION...
Страница 136: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 131 Maintenance...
Страница 151: ...GREE GMV5 INDOOR UNIT SERVICE MANUAL 146 GMV ND160PHS A T GMV ND224PH A T GMV ND280PH A T...
Страница 276: ...JF00302966...