DC Inverter U-match Series Duct Type Unit
41
④
Supply cords of parts of appliances for outdoor use shall not be
lighter than polychloroprene sheathed flexible cord (code
designation 60245 IEC 57).
⑤
Specifications of circuit breaker are based on a working
condition where the working temperature is 40°C. If working
condition changes, please adjust the specifications according to
national standards.
⑥
Adopt 2pc of 0.75mm² power cords to be the communication
cords between indoor and outdoor units. The maximum length is
100m. Please select a proper length according to local
conditions. Communication cords must not be twisted together.
To be in compliance EN 55014, it is necessary to use 8 meters
long wire.
⑦
Adopt 2pc of 0.75mm² power cords to be the communication
cords between wired control and indoor unit. The maximum
length is 30m. Please select a proper length according to local
conditions. Communication cords must not be twisted together.
To be in compliance EN 55014, it is necessary to use 7.5 meters
long wire.
⑧
The wire gauge of communication cord should not be less than
0.75mm². It’s recommended to use 0.75mm² power cords as the
communication cords.
3.3.3 Connection of Power Cord and Communication Cord
(1) For solid wires (as shown below):
1) Use wire cutters to cut off the wire end and then peel away
about 25mm of the insulation layer.
2) Use a screwdriver to unscrew the terminal screw on the
terminal board.