DC Inverter U-match Series Duct Type Unit
40
⑫
The wire gauge of power cord should be large enough.
Damaged power cord or other wires must be replaced by
specialized wires. Wiring work must be done according to
national wiring rules and regulations.
3.3.2 Electrical Parameters
3.3.2.1 Wire Specifications and Fuse Capacity
Model
Power supply
Fuse
capacity
Circuit breaker
capacity
Min. sectional area
of power cord
V/Ph/Hz
A
A
mm
2
Indoor
unit
220-240V ~50/60Hz
3.15
6
1.0
Model
Power supply
Circuit breaker
capacity
Min. sectional area
of power cord
V/Ph/Hz
A
mm
2
GUD35W/A-S
220-240V
~50/60Hz
16
1.5
GUD50W/A-S
16
1.5
GUD71W/A-S
20
2.5
GUD100W/A-S
25
2.5
GUD125W/A-S
32
4.0
GUD140W/A-S
32
4.0
GUD160W/A-S
40
6.0
GUD125W/A-X
380-415V
3N~ 50/60Hz
16
1.5
GUD140W/A-X
16
1.5
GUD160W/A-X
16
1.5
NOTICE:
①
Fuse is located on the main board.
②
Install a circuit breaker at every power terminal near the units
(indoor and outdoor units) with at least 3mm contact gap. The
units must be able to be plugged or unplugged.
③
Circuit breaker and power cord specifications listed in the above
table are determined based on the maximum power input of the
units.