Section 18: Fault Finding
Page 72
18 Fault Finding
18.1 Burner Fault Indication
Whenever a burner lockout occurs the cause is displayed via the reset push button indicator LED on the control box. The colour, sequence
and speed of the indicator LED flashes identify the specific lockout type and the possible causes are listed in Table X-1.
Table 18-1:
Burner fault indication
Lockout description
Lockout time
LED colour
Probable cause
Presence of extraneous light during
standby
After 25 seconds
RED
blinking
• Presence of a false flame signal before the heat
request
Presence of extraneous light detected
during pre-purging
After 25 seconds
RED
blinking
• Presence of false flame signal during pre-purging
Extraneous light detected during
post-purging
After 25 seconds
RED
blinking
• Presence of false flame signal during post-purging
(or pre-heating if the short-circuit socket is not con-
nected
The flame is not detected after the
safety time
After 5 seconds from oil-valve starts
RED
steady ON
• UV sensor defective or dirty
• Oil valve defective or dirty
• Faulty ignition transformer
• Badly regulated burner
• Oil fuel not present
Flame failure during operation
After 3 recycles
RED
blinking
• Badly adjusted burner
• Oil valve defective or dirty
• UV sensor defective or dirty
Fan motor error
Immediate (during pre-purge)
RED, ORANGE
blinking inverted
• Faulty fan motor
• Fan motor not connected
Malfunction in the internal control
circuit that drives the oil valve
Immediate (during pre-purge)
RED, GREEN
blinking inverted
• Faulty oil valve
• Internal control circuit that drives the oil valve faulty
Eeprom error
Immediate (during pre-purge)
ORANGE, GREEN
blinking inverted
• Faulty internal memory
18.2 Burner Fault Diagnostics
Table 18-2:
Burner faults
Faults
Possible cause
Fault
diagnostics
Solutions
The burner does not start when there
is heat demand
Lack of electrical supply
OFF
Check presence of voltage in the L - N the pin plug
Check the conditions of the fuses.
Check that safety thermostat is not in lockout
The UV sensor sees an extraneous
light
GREEN, RED
blinking
Eliminate the extraneous light.
The connections in the control box are
wrongly inserted
OFF
Check and connect all the plugs and sockets
properly.
The burner goes into lockout mode
before or during the pre-purging
The UV sensor sees extraneous light
RED blinking
Eliminate the extraneous light.
Burner runs normally in the pre-purge
and ignition cycle and locks out after
about 5 seconds
The UV sensor is dirty
RED steady ON
Clear it
The UV sensor is faulty
Replace it
Flame moves away or fails
Check pressure and output of the fuel
Check air output
Change nozzle
Check the coil of solenoid valve
Burner starts with an ignition delay
The ignition electrodes are wrongly
positioned
GREEN blinking
Adjust them according to the instructions of this
manual
Air output is too high
Set the air output according to the instructions of this
manual
Nozzle dirty or worn
Replace it
Содержание Aerona3 Series
Страница 57: ...Section 13 Flue System and Air Supply Page 57 Figure 13 8 Flue clearances...
Страница 77: ...Section 19 Spare Parts Page 77 Figure 19 4 15 21kW baffles Figure 19 5 21 26kW baffles...
Страница 84: ...Appendix A Page 84 Appendix A...
Страница 85: ...Appendix A Page 85...
Страница 86: ...Appendix A Page 86...
Страница 87: ...Appendix A Page 87...