Section 3: Oil Storage and Supply System
Page 14
Filter
Fire
valve
Shut-off
valve
Shut-off
valve
A
Sludge
valve
Fill
pipe
Vent
pipe
Level
gauge
Fuel
storage
tank
Fire
valve
sensor
Pump
1 m
Figure 3-2:
Single pipe system
Fire valve
Tankmaster
See
Section 3.2
Sludge
valve
Fill
pipe
Vent
pipe
Fuel
storage
tank
De-aeration device
e.g. Tiger Loop
See Figure 3-1
Fire
valve
sensor
Supply
1 m
Return
Filter
Fire
valve
Shut-off
valve
Shut-off
valve
See
Section 3.2
A
Return
Supply
Non
return
valve
Fire
valve
sensor
Sludge
valve
Fill
pipe
Vent
pipe
Level
gauge
Fuel
storage
tank
1 m
Figure 3-3:
Two pipe system
Figure 3-4:
De-aeration device system
Table 3-5:
Single pipe system maximum pipe runs
Head A
(m)
Maximum pipe run (metres)
10 mm OD pipe
12 mm OD pipe
0.5
10
20
1.0
20
40
1.5
40
80
2.0
60
100
Table 3-6:
Two pipe system maximum pipe runs
Head A
(m)
Maximum pipe run (metres)
10 mm OD pipe
12 mm OD pipe
0
35
100
0.5
30
100
1.0
25
100
1.5
20
90
2.0
15
70
3.0
8
30
3.5
6
20
Содержание Aerona3 Series
Страница 57: ...Section 13 Flue System and Air Supply Page 57 Figure 13 8 Flue clearances...
Страница 77: ...Section 19 Spare Parts Page 77 Figure 19 4 15 21kW baffles Figure 19 5 21 26kW baffles...
Страница 84: ...Appendix A Page 84 Appendix A...
Страница 85: ...Appendix A Page 85...
Страница 86: ...Appendix A Page 86...
Страница 87: ...Appendix A Page 87...