14
AIR CONDITIONING
An air conditioning coil may be installed on the supply side
only
. Coils installed on the return side
will cause condensation on the heat exchanger; this will shorten the heat exchanger life and may
cause products of combustion to enter the house. Wire as per wiring label and diagram.
Height of the coil above the unit supply shall be at least 4” (102 mm).
See A/C coil Manufacturers Requirements.
To check the AC coil total air flow resistance, see procedure at page 39
4 inches minimum
4 inches
minimum
KLR
KLF
HUMIDIFIER
If a humidifier is installed ensure that no water can drip or run from it into the furnace. This
would cause deterioration and void the furnace warranty.