Appliance(s) located in a limited space
Combustion air from outdoors by infiltration and ventilation from inside the building
The opening shall have a total free-flow area of not less than 4,4 cm
2
/kW (1 po
2
/5000 BTU/h) of the
total input rating for the appliance(s) located in a limited space.
Each ventilation opening through the inside wall (venting opening of the combustion air and
ventilation opening) shall have a free-flow area of not less than 22 cm2/kW (1 po2/1000 BTU/h) of
the input rating of the appliance(s) located in the limited space.
4.0 ACCESSORIES INSTALLATION
BLOCKED VENT SWITCH (BVSO)
(FOR CANADIAN INSTALLATION ONLY)
Oil-fired appliances installed in Canada require a blocked vent switch system when installed on a
chimney. A safety switch is included with the furnace to perform this function. It is the installer’s
responsibility to install the switch in accordance with the instructions provided. Not applicable for
direct vent systems.
Field Controls Model: WMO-1 (Manual Reset)
12’’ higher than ground level