GAS FIRED HIGH EFFICIENCY FURNACE 

DOWN FLOW & DIRECT VENT (SEALED COMBUSTION) 

 

MODEL: CMA1-50N & CMA2-75N 
INSTALLATION AND SERVICE MANUAL

 

For installation in:  

1.  

Manufactured Homes 

2.  

Modular Homes/Buildings 

3.  

Site Constructed—Residential (Single Story Dwellings) 

  

 

 

FOR YOUR SAFETY 

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this 
or any other appliance.

 

 

WHAT TO DO IF YOU SMELL GAS 

•  

Do not try to light any appliance.

 

•  

Do not touch any electrical switch; do not use any phone in your building. 

•  

Immediately call your gas supplier from a neighbor’s phone.  

    Follow the gas supplier’s instructions.

      

•  

If you cannot reach your gas supplier, call the fire department.

 

 

 

:

 If the information in these instructions is not followed exactly, a fire or explosion may 

result causing property damage, personal injury, or loss of life. 
 

: Improper installation, adjustment, alteration, service, or maintenance can cause 

injury or property damage.  Refer to this manual.  For assistance or additional information, 
consult a qualified installer, service agency, or fuel supplier. 
 

Do not use this appliance if any part has been underwater.  Immediately call a 

qualified service technician to inspect the appliance and to replace any part of the electrical or 
control system that has been underwater. 
 

 

 

 

 

 

 

 

 

 

 

 

THERMO PRODUCTS, LLC. 

                                       POST OFFICE BOX 217 

     NORTH 

JUDSON, 

IN 

46366

 

 

 

 

 

 

PHONE: (574) 896-2133 

 

 

 
MG-508   

ECN 5135-MA 100615

 

MADE IN USA 

 

 

 

 

 

PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION, INITIAL FIRING, AND BEFORE 
PERFORMING ANY SERVICE OR MAINTENANCE.  THESE INSTRUCTIONS MUST BE LEFT WITH THE USER 
AND SHOULD BE RETAINED FOR FUTURE REFERENCE BY QUALIFIED SERVICE PERSONNEL.

Содержание CMA1-50N

Страница 1: ...ons is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Improper installation adjustment alteration service or maintenance can cause injury o...

Страница 2: ...K CONDENSATE DRAIN LINE AND TRAP ASSEMBLY 26 L ELECTRICAL WIRING 27 V STARTING THE UNIT 32 A SEQUENCE OF OPERATION 32 B INITIAL START UP 34 C ADJUSTMENT OF BTU INPUT RATE 35 D BURNER ADJUSTMENT 36 E...

Страница 3: ...ualified service personnel I SAFETY INFORMATION This and the following page contain reproductions of the various warning and instruction labels placed on the Thermo Pride Condensing Gas Furnaces Pleas...

Страница 4: ...formed by qualified service personnel This and the previous page contain reproductions of the various safety and instruction labels placed on the Thermo Pride Condensing Gas Furnaces Please read and c...

Страница 5: ...ANSI Z233 1 Latest Edition 6 Always install furnace with a duct system that has an external static pressure within the allowable range referenced in specifications 7 Make sure supply air ducts are co...

Страница 6: ...come from bleaches air fresheners or mastics Vapors from such products can form acid compounds when burned in a gas flame Should acid compounds form in your furnace it may reduce the life of the furn...

Страница 7: ...ce LP gas is especially dangerous because the specific gravity of LP gas allows it to accumulate at floor level at a dangerous concentration Heat exchanger oil will burn off on initial firing creating...

Страница 8: ...NSIONS CABINET SIZE SUPPLY AIR OUTLET ELECTRICAL SUPPLY FUSE OR HACR BREAKER TOTAL CURRENT AMPS NOMINAL ANTICIPATOR SETTING FILTER SIZE APPROXIMATE SHIPPING WEIGHT BLOWER DATA BLOWER MODEL MOTOR HORSE...

Страница 9: ...in Gas Conversion Kit AOPS7678 3 These Category Type IV furnaces are shipped completely assembled and wired internally See the Dealer Receiving and Freight Claim Procedure Section of the price guide f...

Страница 10: ...an National Standard ANSI Z223 1 NFPA 54 for all gas fired furnaces d American National Standard ANSI C1 NFPA 70 Electric Code for all electrical field wiring e These gas fired units have been investi...

Страница 11: ...zed with respect to the duct system 2 The furnace installation is only intended for free air return through the furnace door louvers DO NOT connect a ducted return air system directly to the furnace A...

Страница 12: ...lations and services must be performed by qualified service personnel Combustible Floor Base Model 70 BASE Figure 1A Coil Cabinet Model CE113S Note This cabinet cannot be utilized as a cottage base Fi...

Страница 13: ...installations and services must be performed by qualified service personnel Cottage Base Model 01COT BASE Figure 1C NOTE Serves as a plenum for single story applications with exposed supply air system...

Страница 14: ...pening locations see Figure 2 Cut a square opening in the floor for the supply air connector duct Cut the opening 1 inch larger than the square template opening duct requires 1 inch clearance to combu...

Страница 15: ...he other hand This assures a tight connection between the base assembly and the connector duct and that the distribution duct will be full size Use high temperature tape and or high temperature silico...

Страница 16: ...in the floor or ceiling shall not be less than 250 square inches 4 The total free area of openings in the floor or ceiling registers serving the return duct system must be at least 350 square inches...

Страница 17: ...nnection shall be provided directly up stream of the burner to allow burner removal Unions must be of a ground joint type or flange jointed type using a gasket resistant to the applicable gas Pipe dop...

Страница 18: ...must be installed with outside combustion air 3 The flue vent pipe and combustion air pipe must be at least as large as the exhaust vent air intake pipe specified by Thermo Products No reduction in s...

Страница 19: ...e PVC sleeve or coupling to the metal air intake collar on the burner box The screw securing the sleeve or coupling to the collar is sufficient 7 Use the two radiator hose clamps to connect both the e...

Страница 20: ...vent pipe must be supported every 4 feet After making sure the length of the piping is correct glue all connections in place This CMA furnace has been designed to be installed as a direct vent system...

Страница 21: ...tion or its equivalent Outside combustion air must not come from an area that is directly adjacent to a pool hot tub or spa Measures should be taken to prevent the entry of corrosive chemicals or vapo...

Страница 22: ...t vent termination elbow shall be installed in accordance with these instructions and any applicable local codes Refer to Figures 7 and 8 for typical examples of proper terminations a The exhaust vent...

Страница 23: ...rom or 12 inches above any door window or gravity air inlet into a building The bottom of the vent terminal shall be located at least 12 inches above grade c The vent terminal shall not be located ove...

Страница 24: ...All installations and services must be performed by qualified service personnel Figure 9 NFGC Minimum Clearances Between the Vent Terminal and Various Building Features 22...

Страница 25: ...ombustion air terminations shall be checked periodically at least at the start of each heating season for restriction or blockage from foreign material in the exhaust vent or in the air intake piping...

Страница 26: ...eel screen is available from Thermo Products under part no 320219 J CONNECTING THE FURNACE TO ROOF VENT AIR TERMINATIONS The CMA is designed to be vented with either a concentric vent assembly or twin...

Страница 27: ...the roof The outlet inlet of the vent and air intake terminations shall be a minimum of 12 inches above highest anticipated snow level The vent outlet must be installed a minimum of 12 in above the a...

Страница 28: ...the fire stop far enough to engage a PVC coupling that will rest on the fire stop and act as a support Seal between the pipe coupling and fire stop with high temperature RTV silicone sealant see Figu...

Страница 29: ...TION 1 Electrical Branch Supply Circuit Route all electrical wiring to the left side of the furnace The power supply circuit to the furnace must be installed and grounded in accordance with the provis...

Страница 30: ...only 2 wires are required for the furnace a heating application only Electrical Wire Diameter Maximum Recommended Thermostat Wire Length AWG Feet 24 55 22 90 20 140 18 225 Once the furnace is installe...

Страница 31: ...grounded in accordance with local codes and with the National Electrical Code ANSI NFPA NO 70 Latest Edition when an external electrical source is utilized 4 BLOWER MOTOR SPEED WIRING Figure 15 BLOWER...

Страница 32: ...e Rise vs External Static Pressure in WC Speed Tap Static Pressure 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Low 53 55 57 59 63 71 78 ML 42 44 45 48 51 53 59 MH 35 37 38 40 42 45 49 High 31 33 34 36 38 41 44 Blower...

Страница 33: ...rature Rise vs External Static Pressure in WC Speed Tap Static Pressure 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Low 81 83 85 90 90 106 119 ML 65 66 69 72 76 80 87 MH 52 55 56 59 61 64 69 High 45 46 48 50 52 55 59...

Страница 34: ...odule to obtain the desired CFM The unused speeds should then be reconnected to the module in the park positions Refer to figure 15 Refer to section II for blower speed and air flow performance for A...

Страница 35: ...INTERRUPTION SYSTEM SHUTS OFF RESTARTS WHEN POWER IS RESTORED PRESSURE SWITCH SENSES ADEQUATE DIFFERENTIAL PRESSURE CONTACTS CLOSE CONTROL BOARD ENERGIZED INDUCER ENERGIZED POWER IS APPLIED TO THE SI...

Страница 36: ...THE GAS VALVE IS DE ENERGIZED AFTER PROOF OF FLAME LOSS INDUCER STARTS 5 SECOND POST SURGE AND OPTIONAL HUMIDIFIER ARE DE ENERGIZED THE DELAY TO FAN OFF PERIOD BEGINS 120 SECONDS IF SYSTEM IS IN LOCK...

Страница 37: ...to the drain system OPERATING INSTRUCTIONS Turn off power to furnace before it is placed into service The gas piping system must have been leak tested by a qualified heating contractor in accordance...

Страница 38: ...rate for 10 to 15 minutes and proceed as follows 1 Call your gas supplier and ask for the BTU content heating value of one cubic foot of the gas supplied to the installation area An alternate approach...

Страница 39: ...NOT EXCEED 0 3 WC A 0 3 WC adjustment will increase or decrease the input approximately 4 0 Replace screw cap when adjustment is complete The correct input can be assumed if the furnace manifold press...

Страница 40: ...ch installation A lower temperature rise will result in a higher efficiency Temperature rise supply air temperature return air temperature After 10 to 15 minutes of continuous operation the temperatur...

Страница 41: ...as follows a Shut off incoming power b Block return air opening or disconnect blower motor leads c Restore power to furnace d Set thermostat above room temperature calling for heat e When temperature...

Страница 42: ...nd may void the limited warranty on the furnace 6 Review with and encourage the user to read the label reproductions and all warnings and instructions in this manual 7 Recommend that the user have a q...

Страница 43: ...cted 2 CONDENSATE LINE TRAP ASSEMBLY The condensate line must be inspected to make sure it is not blocked All of the lines should be flushed with water to remove any build up of sediment 3 BURNERS If...

Страница 44: ...ning being careful not to bend or damage any of the fins c Once all components are cleaned they must be re installed to their factory produced state Any seals or joints in the flue system which have b...

Страница 45: ...PERFORMED BY QUALIFIED HEATING CONTRACTORS To assist you in troubleshooting this furnace it is equipped with an integrated ignition control with diagnostics These diagnostics evaluate what control sy...

Страница 46: ...high limit switch 6 flashes then pause 115 volt AC power reversed 7 flashes then pause low flame sense signal 8 flashes then pause check ignitor or improper grounding Continuous flashing Flame has bee...

Страница 47: ...K SERVICE SWITCH AND FUSES No CHECK FOR CONTINUITY PROPER CONNECTIONS No Yes Yes REPLACE TRANSFORMER No Yes Yes No No Yes ARE WIRES CONNECTED PROPERLY No CORRECT WIRE CONNECTIONS No Yes Yes No Yes IS...

Страница 48: ...TERMINALS IND IND N AT THE INTEGRATED CONTROL CHECK THE INTEGRATED CONTROL DIAGNOSTIC LED LAMP RESET BY INTERRUPTING POWER TO CONTROL FOR MORE THAN ONE SECOND IF LED STAYS ON CONTINUOUSLY REPLACE INTE...

Страница 49: ...FLAME CHECK Yes CHECK ACROSS THE CIRCULATING AIR BLOWER TERMINALS CIR N HEAT FOR PROPER VOLTAGE REPLACE THE INTEGRATED CONTROL No No Yes DOES THE CIRCULATING AIR FAN COME ON WHEN ENERGIZED No DOES BLO...

Страница 50: ...ISFIED CHECK ALL WIRING FOR LOOSE CONNECTIONS CHECK FOR SHORT IN WIRE TO THERMOSTAT AND CORRECT IF NECESSARY DOES BURNER SHUT OFF WHEN THERMOSTAT IS SATISFIED No DOES THE CIRCULATING AIR BLOWER TURN O...

Страница 51: ...K OPEN 4 FLASHES THEN PAUSE OPEN LIMIT SWITCH OR ROLLOUT SWITCH 6 FLASHES THEN PAUSE 115 VOLT AC POWER REVERSED 7 FLASHES THEN PAUSE LOW FLAME SENSE SIGNAL 8 FLASHES THEN PAUSE CHECK IGNITOR OR IMPROP...

Страница 52: ...All installations and services must be performed by qualified service personnel APPENDIX A REPLACEMENT PARTS 50...

Страница 53: ...All installations and services must be performed by qualified service personnel All installations and services must be performed by qualified service personnel 51 51...

Страница 54: ...All installations and services must be performed by qualified service personnel APPENDIX B WIRING DIAGRAM 52...

Страница 55: ...All installations and services must be performed by qualified service personnel 53...