Appendix D - ADM Event and Error Codes Overview
313875J
79
WSC0
Invalid
Setpoint
Request
The requested controlling
value (pressure or flow) is
outside the limits of the system
Deviation
System incorrectly setup
On the ADM go into the setup screens -> System->
and ensure that all pages have properly defined
values
Shot incorrectly defined
Redefine shot with control parameters within the limits
of the system
WSD0
Invalid Gel
Timer
Definition
The shot that was entered for
the gel timer is not a valid shot.
This must be fixed before the
gel timer will function properly
Deviation
Gel timer shot is below
the minimum dispense
amount or set for a
invalid pressure/flow
Select a different shot or modify existing shot data
The MCM has
determined that the gel
timer shot will not be able
to be executed based
parameters entered in
the ADM
If you are certain that the shot is within parameters,
try running the Learn Mode routine found in the setup
screen Calibration. If the error persists, a gel shot with
reduced control parameters is required.
Error
Code
Error Name
Error Description
Error
Type
Cause
Solution
Содержание VPM 12
Страница 9: ...A Red and B Blue Components 313875J 9...
Страница 11: ...Component Identification 313875J 11 FIG 2 Component Identification ti17702a AJ AF AL AD AC VPM 25 shown...
Страница 12: ...Component Identification 12 313875J VPM 12 FIG 3 ti17703a AL AA AK AH AE AB AD AF AJ AL AD AC AC...
Страница 50: ...Maintenance 50 313875J...
Страница 86: ...Appendix E USB Operation 86 313875J...