Advanjet HV-2000C Jet Controller Setup and Operation
3A5856A
Appendix 4-1:
HD26 Pin Assignments (Continued)
11
Analog input
AIN 5
11-bit res. channel, software-selectable ranges
unipolar: 1, 2, 2.5, 5, 10, 20 V DC; bipolar ± 1, ±2, ±5, ±10 V DC;
4 channels can be hardware-configured for 4
–20 mA;
1 MÙ input impedance, up to 4,100 samples/s
Buffered A/D
Converter Inputs
12
Analog Input
AIN 7
11-bit res. channel, software-selectable ranges
unipolar: 1, 2, 2.5, 5, 10, 20 V DC; bipolar ± 1, ±2, ±5, ±10 V DC;
4 channels can be hardware-configured for 4
–20 mA;
1 MÙ input impedance, up to 4,100 samples/s.
Buffered A/D
Converter Inputs
13
Analog output
AOUT 1
12-bit res. channel, buffered, 0
–10 V DC, ±10 VDC,
and 4
–20 mA, update rate 12 kHz.
D/A Converter
Outputs
14
GND
ANALOG GROUND
15
No connection.
16
No connection.
17
No connection.
18
Heater Alarm Common (Output)
19
Fluid Pressure Alarm Common (Output)
Optional alarm. Not normally programmed for use.
Pressure Alarm
Input/Output
Circuit (AP-
C30K/C31K/C33K)
20
Fluid Pressure Alarm 2 (Output)
Optional alarm. Not normally programmed for use.
21
Fluid Pressure Alarm 1 (Output)
Optional alarm. Not normally programmed for use.
22
Jet Pressure Alarm Common (Output)
Optional alarm. Not normally programmed for use.
23
Jet Pressure Alarm 2 (Output)
Optional alarm. Not normally programmed for use.
24
Jet Pressure Alarm 1 (Output)
Optional alarm. Not normally programmed for use.
25
Heater Alarm 1 (Output)
Single Pole, Single Throw, Normally open relay contact, 3A, 250
VAC. When closed, pin 25 is connected to pin 18, Heater Alarm
Common.
Optional alarm. Not normally programmed for use.
May be configured to create an alarm for 12 different fault conditions.
26
Heater Alarm 2 (Output)
Single Pole, Single Throw, Normally open relay contact, 3A, 250
VAC. When closed, pin 26 is connected to pin 18, Heater Alarm
Common.
Optional alarm. Not normally programmed for use.
May be configured to create an alarm for 12 different fault conditions.