Installation
311075ZAB
17
Table 2: Electrical Requirements
Model
Required Power Source
Power Cord Connector
120 V, 1 phase, 50/60 Hz, two 15 ft
(4.5 m) power cords, Heated
Two separate, dedicated circuits
rated at minimum of 15 A each
240 V, 1 phase, 50/60 Hz, two 15 ft
(4.5 m) power cords, Heated
Two separate, dedicated circuits
rated at minimum of 10 A each
240 V, 1 phase, 50/60 Hz, one 15 ft
(4.5 m) power cord, Heated
Single dedicated circuit rated at
minimum of 16 A
120 V, 1 phase, 50/60 Hz, one 15 ft
(4.5 m) power cord, Nonheated
Single dedicated circuit rated at
minimum of 15 A
240 V, 1 phase, 50/60 Hz, one 15 ft
(4.5 m) power cord, Nonheated
Single dedicated circuit rated at
minimum of 8 A
Table 3: Extension Cord Requirements
Model
Required Wire Size
Up to 50 ft (15 m)
Up to 100 ft (30 m)
Nonheated and two cord heated
models
AWG 14
AWG 12
Single cord heated model
AWG 12
AWG 10
NOTE:
Cords must be 3-conductor grounded, rated for your environment.
F
IG
. 5 Use Two Separate Circuits for Two Cord Models
Two NEMA 5-15T
Two IEC 320, with two
local adapters:
Euro CEE74 Adapter
Australia/China Adapter
One NEMA 6-20P
One NEMA 5-15T
One NEMA 6-20P
1
Ensure no other high amp loads are connected
while running Reactor E-10.
To verify separate circuits, plug in Reactor E-10
or a worklight and cycle breakers on and off.
1
2
To avoid electric shock, always unplug both cords
before servicing Reactor E-10.
1
Heater Power
Motor Power
TI7061a
2