E-Flo Plus Features
311596A
17
* Calibration parameter – user calibration that gets
saved. These parameters are not initialized to 0. For
example, if Lower Size (Pr 20.03) is calibrated to be
1500cc, this will be saved in a memory of AppsLite mod-
ule. Pr 20.03 will then be initialized to 1500 at every sys-
tem reset and start-up.
** Load Defaults: Yes indicates that a default value will
be loaded if Load Defaults function is invoked.
*** Run mode is not a save parameter. Any changes to
this parameter will only stay active until the drive is
reset. The drive will default to Programmed Cam mode
during the power-up cycle.
****Initial value is provided by Graco.
20.17
Flow Indicator. If Pr 20.15 = 0, the flow is
displayed in English units - gallons per
minute [gpm], and if Pr 20.15 = 1, the flow is
displayed in Metric units - liters per minute
[lpm].
Indicator [gpm/lpm]
20.18
BPR valve control (0 = Disable, 1 = Enable;
controls digital I/O 3, 0 = 0V, 1 = 24V)
0 (Calibration Pr)
0
1
Yes
20.19
Average Cycle Rate Indicator
Indicator
20.20
Graco defined software version major
Indicator
20.21
Graco defined software version minor
Indicator
20.24
Average Motor Current (A)
Indicator
20.25
Keypad Run/Stop Command (0=Disable
keypad run/stop control, 1=Motor Stop
Command (same as Pr 6.42=193), 2=Motor
Run Command (same as Pr 6.42=195)
0
0
2
Yes
20.26
Reset Batch Cycle Counter
0
0
1
No
20.27
Grand Cycle Count - First 4 places -
yyyy9999
Indicator
20.28
Grand Cycle Count - The next 4 places -
9999xxxx.
Indicator
20.29
Batch Cycle Count - First 4 places -
yyyy9999
Indicator
20.30
Batch Cycle Counter - The next 4 places -
9999xxxx
Indicator
20.31
Average Pressure [psi]
Indicator
20.32
Pressure Range [psi]
Indicator
20.33
Pressure Sensor Trip (used for calibration)
Indicator
20.34
Low Calibration Point (refer to pressure cali-
bration instructions, page 9)
X**** (Calibration
parameter)
0
10000
No
20.35
System Calibration Pressure (250 - 280 psi)
X (Calibration parame-
ter)
100
500
No
20.36
High Calibration Point (refer to sensor cali-
bration instructions, page 9)
X (Calibration parame-
ter)
0
10000
No
20.37
UL/ATEX Motor Select
0 (Calibration parame-
ter)
0 (UL)
1 (ATEX)
Yes
20.38
Analog Speed Potentiometer Control (0 =
Disable, 1 = Enable)
0 (Calibration parame-
ter)
0
1
Yes
20.40
System Prime/Flush Enable - commands
motor to run at 75Hz for 2 minutes (0=Dis-
able/Stop, 1=Enable/Start)
0
0
1
No
Table 2: E-Flo Plus Calibration Parameters / Modbus Map