E-Flo Plus Calibration
12
311596A
Factory Defaults
E-Flo Plus System Specific Parameters (menu 20
parameters)
All of the E-Flo Plus features are controlled by menu 20
parameters. VFDs are shipped with these parameters
set to default values (refer to Table 2 on page 16 for
more information). Factory defaults can be loaded as fol-
lows:
1.
Disable the drive through Secure Disable (if a Graco
Local Control Box is used, press the red
mushroom-type Secure Disable button).
2.
Navigate to Pr 20.16 and set its value to 1234. At
this time the program defaults will be loaded and
number 1234 will automatically be replaced by 0.
E-Flo Plus Motor Specific Parameters
VFDs are shipped with all motor parameters defaulted to
a Graco UL motor. It is essential to check motor selec-
tion (page 9) and either:
•
if Graco ATEX motor is used, reload motor defaults
(see Graco Motors, page 9)
•
if non-Graco motor is used, set all motor parameters
(see Non-Graco Motors, page 9).
SMARTCARD Defaults
Default Graco parameter values for menus 0 through 22
are saved on SMARTCARD in location #101, as differ-
ences from the drive defaults (Code 4101); see the Con-
trol Techniques manual for further information. Use
Code 6101 to load Graco defaults.
System-related Graco default parameters (menu 20)
may be loaded by navigating to Pr 20.16 and setting its
value to 1234. Note that Pr 20.16 will be automatically
reset back to 0.
Complete System Reload
A complete system reload may be necessary because
of an error in calibration or accidental parameter alter-
ation.
1.
Disconnect power to the VFD.
2.
Remove all solutions modules from the VFD
(AppsLite and Ethernet). Reconnect power.
3.
Navigate to Pr 0.00 and set its value to 1244.
4.
Press the red Stop/Reset button. Number 1244 will
be automatically replaced by 0 as an indication that
all VFD parameters are reset to defaults.
5.
Navigate to Pr 0.00, set its value to 1000, and press
red Stop/Reset button to save the changes. Number
1000 will be automatically replaced by 0.
6.
Disconnect power from the VFD, reinstall all mod-
ules, and reconnect power.
7.
Navigate to Pr 17.20 and set it to ON.
8.
Navigate to Pr 17.21 and set it to ON.
9.
Navigate to Pr 17.00, set its value to 1000, and
press red Stop/Reset button. Number 1000 will be
automatically reset to 0 as an indication that
changes have been saved.
10. Load system-specific calibration from the SMART-
CARD (if saved at initial calibration).
a.
Graco defaults are loaded as differences from
VFD defaults in memory location #101. Navi-
gate to Pr 0.00, set its value to 6101, and press
red Stop/Reset button.
b.
Recommended memory location for customer
calibration is #202. Navigate to Pr 0.00, set its
value to 6202, and press red Stop/Reset button.
11. If SMARTCARD is not available or if initial calibra-
tion was not saved to SMARTCARD, perform the fol-
lowing steps:
a.
Load Graco system defaults - set Pr 20.16 to
1234.
b.
Repeat E-Flo Plus Calibration, beginning with
Calibrate and Autotune the Motor on page 9
and continuing with steps 1-9 of the calibration
12. Reset program module (and Ethernet/communica-
tion modules) by navigating to Pr 0.00, setting its
value to 1070, and pressing the red Stop/Reset but-
ton on keypad display.