background image

Rev. A  92149901

3

Install Bung Adapter and Suction Pipe

Make sure all threaded fuel connections are wrapped 

with three to four turns of thread tape or a pipe sealant 

approved for use with petroleum fuels.
•  Tighten the bung adapter snugly on the fuel tank.
•  Place the union ring gasket into the inlet fitting on the 

bottom of the pump.

•  Thread the suction pipe into the inlet fitting and tighten 

until snug.

Install Pump on Tank

•  Clean the tank interior of all dirt and foreign material.
•  Extend the suction pipe to its full length and insert 

into the tank opening.  (Figure 1)

FIGURE 1

The suction pipe 

will adjust to the 

length needed to 

rest on the tank 

bottom.

•  Place the pump on the bung adapter and tighten the 

union ring securely with a pipe wrench. Make sure 

the union ring is not cross-threaded.

NOTE: To prevent pressure buildup and possible fuel 

leaks through the nozzle, make sure the tank is vented. 

A vent cap rated at 3 psi or less is recommended.

Install Electrical Connections

This pump is designed for use with 120-volt power. Do not 

attempt installation on 12-volt, 24-volt, or 230-volt power 

sources.

To avoid personal injury, these instructions must be followed.

 

WARNING

It is important to exercise more than ordinary care with 

electrical installation and maintenance. Failure to follow 

these electrical connection instructions could result in 

death or serious injury from shock, fire, or explosion.
Electrical wiring and connections must be made only by 

a licensed electrician in accordance with national, state, 

and local electrical codes regarding Class I, Division 1 

requirements as well as NFPA Code 70 and 30. Other 

codes may apply.
Install UL Listed, rigid metal conduit and code-specified 

gas-oline and oil-resistant wire with ground wire from the 

switch box to the pump electrical box and use proper 

seal offs.

To avoid personal injury, make sure power is disconnected 

before removing coverplates.

 

WARNING

•  Remove the electrical coverplate. (Figure 2) Be careful not 

to damage gasket.

FIGURE 2

•  Route the wiring and conduit to the pump.
•  Attach the ground wire to the pump’s green ground 

wire.

To avoid personal injury, the pump must be properly grounded.

 

WARNING

•  Attach wiring to pump wires.
•  Position all wires inside the pump’s electrical cavity.
•  Replace the electrical coverplate.

Install Hose and Nozzle

NOTE:  If  installing  accessories  such  as  flow  meters 

or  filters,  do  so  now,  following  the  manufacturer’s 

instructions.

After sealing the threads, tighten the hose into the pump 

outlet and the nozzle on the hose. The nozzle can be 

placed in he nozzle hanger only when the pump is off.
NOTE: The nozzle holder allows the pump to be locked 

when the nozzle is in place.

OPERATION

ALWAYS FOLLOW SAFETY PRECAUTIONS WHEN 

OPERATING THIS EQUIPMENT. REVIEW THE 

SAFETY INSTRUCTIONS. 

Before each use, repair 

leaks around seals or connections. Make sure hoses 

are in good condition and connections are tight. Make 

sure the work area is dry. 

MAKE SURE THE PUMP IS 

PROPERLY GROUNDED.

 Repair any corroded or dam-

aged wiring before use. Ensure the tank contains enough 

fuel. Make sure the fuel is not contaminated with debris.

Содержание M-1115S

Страница 1: ...ne methanol ethanol diesel fuel up to 20 biodiesel and kerosene Please take all due pre cautions when handling these flammable liquids Your safety is important to us Also to assure the longest possibl...

Страница 2: ...4 8 feet 1 5 m with diesel 5 8 feet 1 8 m with gasoline If you require a greater initial prime height coat the gears with fluid by removing the plug on the top of the pump and pour a small quantity o...

Страница 3: ...by a licensed electrician in accordance with national state and local electrical codes regarding Class I Division 1 requirements as well as NFPA Code 70 and 30 Other codes may apply Install UL Listed...

Страница 4: ...emicals or herbicides Dispensing any fluid other than those listed in this manual will damage the pump Use of the pump with unauthorized fluids will void the warranty To Clean or Replace Strainer Turn...

Страница 5: ...thepoppetcavitythrough the top outlet port PushdownonthepoppetuntilthepoppetO ring is exposed inside the housing Figure 7 FIGURE 7 Using a clean cloth rotate the poppet and clean it thoroughly To remo...

Страница 6: ...ck wires to the switch Cut the wires close to the wire nut leaving the maximum possible length to the pump Loosen the hex nut on the switch mounting plate and remove the defective switch Strip approxi...

Страница 7: ...ntil the motor is flush against the pump housing Tighten the motor to the pump housing Check for proper installation by working a 0015 feeler gauge around the motor flange The gauge shall not fit be t...

Страница 8: ...ed Remove the bypass poppet spring and O ring Clean cavity Inspect and replace components as necessary C LOW FLOWRATE 1 Poor connections or low voltage Make sure electrical connections are secure Also...

Страница 9: ...Cover Gasket 1 13 119096 4 Switch and Circuit Breaker Assembly 1 14 110026 6 Switch Coverplate O Ring 1 15 110276 02 Switch Coverplate Assembly 1 16 110032 1 Union Ring Gasket 1 17 11030302 Cover Noz...

Страница 10: ...e defaced to indicate that the equipment may no longer meet the requirements for ULListing This does not apply to prod ucts serviced outside the factory under the UL program for Rebuilt Motors for Use...

Страница 11: ......

Страница 12: ...duct has been altered or modified outside the warrantor s duly appointed representative B the product has been subjected to neglect misuse abuse or damage or has been installed or operated other than...

Отзывы: