Rev. A 92149901
3
Install Bung Adapter and Suction Pipe
Make sure all threaded fuel connections are wrapped
with three to four turns of thread tape or a pipe sealant
approved for use with petroleum fuels.
• Tighten the bung adapter snugly on the fuel tank.
• Place the union ring gasket into the inlet fitting on the
bottom of the pump.
• Thread the suction pipe into the inlet fitting and tighten
until snug.
Install Pump on Tank
• Clean the tank interior of all dirt and foreign material.
• Extend the suction pipe to its full length and insert
into the tank opening. (Figure 1)
FIGURE 1
The suction pipe
will adjust to the
length needed to
rest on the tank
bottom.
• Place the pump on the bung adapter and tighten the
union ring securely with a pipe wrench. Make sure
the union ring is not cross-threaded.
NOTE: To prevent pressure buildup and possible fuel
leaks through the nozzle, make sure the tank is vented.
A vent cap rated at 3 psi or less is recommended.
Install Electrical Connections
This pump is designed for use with 120-volt power. Do not
attempt installation on 12-volt, 24-volt, or 230-volt power
sources.
To avoid personal injury, these instructions must be followed.
WARNING
It is important to exercise more than ordinary care with
electrical installation and maintenance. Failure to follow
these electrical connection instructions could result in
death or serious injury from shock, fire, or explosion.
Electrical wiring and connections must be made only by
a licensed electrician in accordance with national, state,
and local electrical codes regarding Class I, Division 1
requirements as well as NFPA Code 70 and 30. Other
codes may apply.
Install UL Listed, rigid metal conduit and code-specified
gas-oline and oil-resistant wire with ground wire from the
switch box to the pump electrical box and use proper
seal offs.
To avoid personal injury, make sure power is disconnected
before removing coverplates.
WARNING
• Remove the electrical coverplate. (Figure 2) Be careful not
to damage gasket.
FIGURE 2
• Route the wiring and conduit to the pump.
• Attach the ground wire to the pump’s green ground
wire.
To avoid personal injury, the pump must be properly grounded.
WARNING
• Attach wiring to pump wires.
• Position all wires inside the pump’s electrical cavity.
• Replace the electrical coverplate.
Install Hose and Nozzle
NOTE: If installing accessories such as flow meters
or filters, do so now, following the manufacturer’s
instructions.
After sealing the threads, tighten the hose into the pump
outlet and the nozzle on the hose. The nozzle can be
placed in he nozzle hanger only when the pump is off.
NOTE: The nozzle holder allows the pump to be locked
when the nozzle is in place.
OPERATION
ALWAYS FOLLOW SAFETY PRECAUTIONS WHEN
OPERATING THIS EQUIPMENT. REVIEW THE
SAFETY INSTRUCTIONS.
Before each use, repair
leaks around seals or connections. Make sure hoses
are in good condition and connections are tight. Make
sure the work area is dry.
MAKE SURE THE PUMP IS
PROPERLY GROUNDED.
Repair any corroded or dam-
aged wiring before use. Ensure the tank contains enough
fuel. Make sure the fuel is not contaminated with debris.
Содержание M-1115S
Страница 11: ......