•  know and follow all safety precautions when handling 

petroleum fuels.

•  insure that all equipment operators have access to 

adequate instructions concerning safe operating and 

maintenance procedures.

Observe all safety precautions concerning safe handling 

of petroleum fuels.
To ensure safe operation, all fuel transfer systems must 

be properly grounded. Proper grounding means a continu-

ous metal-to-metal contact from one component to the 

next, including tank, bung, pump, meter, filter, hose and 

nozzle. Care should be taken to ensure proper grounding 

during initial  installation and after any service or repair 

procedures. For your safety, please take a moment to 

review the warnings below.
To prevent physical injury, observe precautions against 

fire or explosion when dispensing fuel. Do not operate 

the system in the presence of any source of ignition 

including running or hot engines, lighted cigarettes, or 

gas or electric heaters. 
Observe precautions against electrical shock when oper-

ating the system. Serious or fatal shock can result from 

operating electrical equipment in damp or wet locations.
Inspect external pump wiring regularly to make sure it 

is in good condition. To avoid electrical shock, use extra 

care when connecting the pump to power.
Avoid prolonged skin contact with petroleum fuels. Use 

protective goggles, gloves and aprons in case of splash-

ing or spills. Change saturated clothing and wash skin 

promptly with soap and water.
Observe precautions against electrical shock when 

servicing
the pump. 

Always

 disconnect power before repairing 

or servicing. 

Never

 apply electrical power to the system 

when any of the coverplates are removed.
If using solvent to clean pump components or tank, 

observe the solvent manufacturer’s recommendations 

for safe use and disposal.

INSTALLATION

This pump is designed to self-prime with dry gears. 

Expect suction lift as follows:
Manual Nozzle: 

5.5 feet (1.7 m) with diesel 

6.7 feet (2.1 m) with gasoline

Automatic Nozzle:  4.8 feet (1.5 m) with diesel 

5.8 feet (1.8 m) with gasoline

If you require a greater initial prime height, coat the 

gears with fluid by removing the plug on the top of the 

pump and pour a small quantity of motor oil into the gear 

cavity. Replace the plug and try again. A foot valve with 

pressure relief may be needed to maintain prime.

GENERAL  INFORMATION

The purpose of this manual is to assist you in install-

ing,  operating and maintaining your GPI pump. This 

manual covers the 120-volt AC electric gear pump, model 

M-1115S-Methanol.

The pump should be connected to a 120-volt AC power 

source.

An automatic bypass valve prevents pressure build 

up when the pump is on with the nozzle closed. To 

avoid damage, do not run the pump more than 10 

minutes with the nozzle closed.

The duty cycle of this pump is 30 minutes ON and 30 

minutes OFF. Allow the pump to cool for 30 minutes.
This pump is specifically designed for use with methanol 

and ethanol. The pump is also compatible with gasoline, 

diesel fuel (up to 20% biodiesel blends such as B20) and 

kerosene. 

Do not 

use this pump for dispensing any fluids 

other than those for which it was designed. To do so may 

damage pump components and will void the warranty.
The pump is designed to operate with the appropriate 

AC voltage at the motor leads and the ratings are de-

termined at this voltage.
Do not leave the system running with fluids. “Dry running” 

can damage the pump.
Do not pump the tank completely dry, as contaminants 

from the bottom of the tank may enter the pump.

SAFETY  INSTRUCTIONS

  The following safety alert symbols are used in 

this manual. Obey all safety messages that follow 

this symbol to avoid possible injury or death.

 

DANGER

 

DANGER

 indicates a haz-

ardous situation which, if 

not avoided, will result in 

death or serious injury.

 WARNING

 

WARNING

 indicates a 

hazardous situation which, 

if not avoided, could result 

in death or serious injury.

 CAUTION

 

CAUTION

 indicates a haz-

ardous situation which, if 

not avoided, may result in 

minor or moderate injury.

It is your responsibility to:

•  know and follow applicable national, state, and local 

safety codes pertaining to installing and operating 

electrical equipment for use with flammable liquids.

Содержание M-1115S

Страница 1: ...ne methanol ethanol diesel fuel up to 20 biodiesel and kerosene Please take all due pre cautions when handling these flammable liquids Your safety is important to us Also to assure the longest possibl...

Страница 2: ...4 8 feet 1 5 m with diesel 5 8 feet 1 8 m with gasoline If you require a greater initial prime height coat the gears with fluid by removing the plug on the top of the pump and pour a small quantity o...

Страница 3: ...by a licensed electrician in accordance with national state and local electrical codes regarding Class I Division 1 requirements as well as NFPA Code 70 and 30 Other codes may apply Install UL Listed...

Страница 4: ...emicals or herbicides Dispensing any fluid other than those listed in this manual will damage the pump Use of the pump with unauthorized fluids will void the warranty To Clean or Replace Strainer Turn...

Страница 5: ...thepoppetcavitythrough the top outlet port PushdownonthepoppetuntilthepoppetO ring is exposed inside the housing Figure 7 FIGURE 7 Using a clean cloth rotate the poppet and clean it thoroughly To remo...

Страница 6: ...ck wires to the switch Cut the wires close to the wire nut leaving the maximum possible length to the pump Loosen the hex nut on the switch mounting plate and remove the defective switch Strip approxi...

Страница 7: ...ntil the motor is flush against the pump housing Tighten the motor to the pump housing Check for proper installation by working a 0015 feeler gauge around the motor flange The gauge shall not fit be t...

Страница 8: ...ed Remove the bypass poppet spring and O ring Clean cavity Inspect and replace components as necessary C LOW FLOWRATE 1 Poor connections or low voltage Make sure electrical connections are secure Also...

Страница 9: ...Cover Gasket 1 13 119096 4 Switch and Circuit Breaker Assembly 1 14 110026 6 Switch Coverplate O Ring 1 15 110276 02 Switch Coverplate Assembly 1 16 110032 1 Union Ring Gasket 1 17 11030302 Cover Noz...

Страница 10: ...e defaced to indicate that the equipment may no longer meet the requirements for ULListing This does not apply to prod ucts serviced outside the factory under the UL program for Rebuilt Motors for Use...

Страница 11: ......

Страница 12: ...duct has been altered or modified outside the warrantor s duly appointed representative B the product has been subjected to neglect misuse abuse or damage or has been installed or operated other than...

Отзывы: