TROUBLE
POSSIBLE CAUSE
PROBABLE REMEDY
MOTOR RUNS, BUT
PUMP FAILS TO
DELIVER WATER
CIRCUIT BREAKER
TRIPS OR FUSE
BLOWS WHEN
PUMP STARTS
MOTOR RUNS FOR
A SHORT TIME,
THEN STOPS
PUMP RUNS BUT
ONLY DELIVERS A
SMALL AMOUNT
OF WATER
OM-06617
SE SERIES
TROUBLESHOOTING
10
TROUBLESHOOTING (Cont'd)
Review all SAFETY information in Section A.
Vertical pumping distance is too high.
Reduce distance or change the
discharge fittings of the pump.
Strainer clogged.
Check and clean as required.
Hardened mud or sludge in pump.
Check and clean.
Damaged power cable.
Inspect and replace as required.
Liquid level device fouled with mud
Clean liquid level device(s).
or foreign material.
Float type sensing device tangled or
Check installation for free movement
obstructed.
of float.
Strainer or impeller clogged.
Check and clean as required.
Circuit breaker or fuse too small.
Check (must be 15 amps).
Strainer or impeller clogged.
Check and clean as required.