ios
Android
Power
BT SERIES USER MANUAL
AC-COUPLED BATTERY STORAGE RETORFIT
Jiangsu GoodWe Power Supply Technology Co.,Ltd
No.90 Zi Jin Road, SND, Jiangsu, China.
www.goodwe.com
[email protected]
340-00330-00
Figure 2.3.1-1
Figure 2.3.1-2
Figure 2.3.1-3
For inverter’s protection and convenient maintenance, mounting location for inverter should be
selected carefully based on the following rules:
Any part of this system shouldn’t block the switch and breaker to disconnected inverter from DC and
AC power.
Rule 1.
Inverter should be installed on a solid surface, where is suitable for inverter’s dimensions and
weight.
Rule 2.
Inverter installation should stand vertically or lie on a slop by max 15° (Figure 2.3.1-1)
Rule 3.
Ambient temperature should be lower than 45°C
(High ambient temperature will cause power derating of inverter.)
Rule 4.
The installation of inverter should be protected under shelter from direct sunlight or bad Rule
weather like snow, rain, lightning etc. (Figure 2.3.1-2)
Rule 5.
Inverter should be installed at eye level for convenient maintenance.
Rule 6.
Product label on inverter should be clearly visible after installation.
Rule 7.
Leave enough space around inverter following the values in Figure 2.3.1-3.
2.3 MOUNTING
2.3.1 SELECT MOUNTING LOCATION
2.1 UNACCEPTABLE INSTALLATIONS
INSTALLATION INSTRUCTIONS
02
Pin Terminal × 12
User Manual × 1
Quick Installation
Guide × 1
2.2 PACKING LIST
BACK-UP CANNOT CONNECT IN PARALLEL.
ONE BATTERY BANK CANNOT BE CONNECT TO MULTIPLE
INVERTERS.
INVERTER BATTERY INPUT CANNOT CONNECT TO
INCOMPATIBLE BATTERIES.
BACK-UP SIDE CANNOT CONNECT TO GRID.
ON-GRID OR BACK-UP SIDE CANNOT CONNECT
TO ANY AC GENERATOR.
ONE METER CANNOT CONNECT TO MULTIPE
INVERTERS. AND DIFFERENT CT CANNOT CONNECT
TO A SAME LINE CABLE.
300mm
500mm
200mm
200mm
300mm
Back-Up
Back-Up
Back-Up
On-Grid
Back-Up
On-Grid
Generator
Battery
Battery
Battery
Incompatible battery
Load
Upward
Downward
Front
Both sides
---------- 300mm
------ 500mm
------------- 300mm
-------- 200mm
Please avoid the following installations
,
which will damage the system or the Inverter.
On receiving the hybrid inverter, please check to make sure all the components as below are not missing
or broken.
PE terminal × 1
Expansion bolts×4
AC Cover×1
Pan head screw×6
Smart Meter *1
with 3 CT
Positive BAT Plug×1
SmartMeter
Negative BAT Plug×1
Inverter×1
Wall-mounted
Bracket×1
Inverter cannot be installed near flammable, explosive or strong electro-magnetic equipment.