background image

5

5000

4500

4000

3500

3000

2500

2000

1500

1000

500

0      1      2      3      4       5      6      7      8       9

10

LEAK(S)
PRESENT

MINUTES

V

AC

U

U

M

 

IN

 

M

IC

RON

S

CONDENSIBLES OR SMALL
LEAK PRESENT

NO LEAKS
NO CONDENSIBLES

If the pressure rises to 1000 microns or less and remains
steady the system is considered leak-free; proceed to
startup.

If pressure rises above 1000 microns but holds steady
below 2000 microns, moisture and/or noncondensibles
may be present or the system may have a small leak.
Return to step 2: If the same result is encountered check
for leaks as previously indicated and repair as necessary
then repeat evacuation.

If pressure rises above 2000 microns, a leak is present.
Check for leaks as previously indicated and repair as nec-
essary then repeat evacuation.

Refer to the Remote Condensing Unit Service Manual for more
detailed instructions on system evacuation, preliminary charge
adjustment, and final charge adjustment.

Electrical Connections

HIGH VOLTAGE!

 

Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death due to electric shock.
Wiring must conform with NEC or CEC and all
local codes. Undersized wires could cause
poor equipment performance, equipment damage
or fire.

WARNING

To avoid the risk of fire or equipment damage, use
copper conductors.

WARNING

NOTICE

Units with reciprocating compressors and non-bleed TXV’s
require a Hard Start Kit.

This unit is designed for three phase operation. DO NOT OP-
ERATE ON A SINGLE PHASE POWER SUPPLY. Measure
the power supply to the unit. The supply voltage 

must

 be in

agreement with the unit rating plate power requirements.

RATED 

VOLTAGE

MINIMUM SUPPLY

VOLTAGE

MAXIMUM SUPPLY

VOLTAGE

208/230V

197

253

460V

414

506

The condensing unit rating plate lists pertinent electrical data
necessary for proper electrical service and overcurrent protec-
tion.  Wires should be sized to limit voltage drop to 2% (max.)
from the main breaker or fuse panel to the condensing unit.
Consult the NEC, CEC, and all local codes to determine the
correct wire gauge and length. The wire size must be sufficient
to carry the Minimum Circuit Ampacity (MCA) listed on the
serial plate.

The supply voltage can be unbalanced (phase to phase) within
2%.  The following formula can be used to determine the per-
centage of voltage unbalance for your unit.

Percentage
Voltage
Unbalance

=

Max. Voltage Deviation Form

Average Voltage
Average Voltage

Example:

L1-L2 = 220V
L2-L3 = 216V

Average Voltage

=

(220 + 216 + 213)/3

=

649/3

Maximum Deviation from Average = 220 - 216 = 4

% Voltage Unbalance = 100 x (4/216)

= 400/216

10

15

20

25

30

35

40

45

14

75

50

37

NR

NR

NR

NR

NR

12

118

79

59

47

NR

NR

NR

NR

10

188 125

95

75

63

54

NR

NR

8

301 201 150 120 100

86

75

68

6

471 314 235 188 157 134 118 110

*Based on NEC 1996

MAXIMUM ALLOWABLE LENGTH IN FEET

TO LIMIT VOLTAGE DROP TO 2%

Minimum Circuit Ampacity (MCA)

Wire 

Size

(AWG)

Содержание CONDENSING AC UNIT

Страница 1: ...s no responsibility for equip ment installed in violation of any codes or regulations The United States Environmental Protection Agency EPA has issued various regulations regarding the introduc tion and disposal of refrigerants Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines Should you have any questions please contact the local offi...

Страница 2: ...rant used Store cylinders in a cool dry place Never use a cy linder as a platform or a roller Another important consideration in selecting a location for the unit s is the angle to obstructions Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance Corner installations are strongly discouraged 12 12 60 24 Thi...

Страница 3: ... type hanger Keep both lines separate and always insulate the suction line Suct Liq Suct Liq Suct Liq 7 1 2 1 1 8 5 8 1 3 8 5 8 1 3 8 5 8 10 1 3 8 5 8 1 5 8 5 8 1 5 8 5 8 Cond Unit Tons REFRIGERANT LINE LENGTH ft 0 24 25 49 50 74 Line Diameter In OD Full rating line size Lines greater than 74 feet in length or vertical elevation changes more than 50 feet refer to the Remote Cooling Service Manual ...

Страница 4: ...isk of fire or explosion never use oxygen high pressure air or flammable gases for leak testing of a refrigeration system WARNING To avoid possible explosion the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve The pressure relief valve must be set to open at no more than 150 psig WARNING Pressure test the system using dry nitrogen and soapy water to lo...

Страница 5: ... NOTICE Units with reciprocating compressors and non bleed TXV s require a Hard Start Kit This unit is designed for three phase operation DO NOT OP ERATE ON A SINGLE PHASE POWER SUPPLY Measure the power supply to the unit The supply voltage must be in agreement with the unit rating plate power requirements RATED VOLTAGE MINIMUM SUPPLY VOLTAGE MAXIMUM SUPPLY VOLTAGE 208 230V 197 253 460V 414 506 Th...

Страница 6: ...e Compressor Rotation Use care when handling scroll compressors Dome temp eratures could be hot CAUTION Three phase scrolls are power phase dependent and can com press in more than one direction Verify proper rotation for three phase compressors by ensuring the suction pressure drops and discharge pressure rises when the compressor is energized NOTE When operated in re verse a three phase scroll c...

Страница 7: ...p plication should have a subcooling of 11 2 ºF and su perheat of 9 1 ºF a If subcooling and superheat are low adjust TXV to 9 1 ºF superheat then check subcooling NOTE To adjust superheat turn the valve stem clock wise to increase and counter clockwise to decrease b If subcooling is low and superheat is high add charge to raise subcooling to 11 2ºF then check superheat c If subcooling and superhe...

Страница 8: ...oil Clean or replace filters 7 Flash gas in the liquid line 7 Excessive liquid line drop Check liquid line size 8 Quantity of air through evaporator not adequate 8 Increase the blower speed 1 Expansion valve stuck open 1 Correct valve action or replace the valve 2 Expansion valve bulb not in contact with 2 Fasten bulb securely to suction line suction line 3 Suction and or discharge valve leaking o...

Отзывы: