Example:
A 7 ½ Ton unit is to be installed. The distance from the 
building to the unit is 75’. Calculate the minimum wire size 
assuming no more than 2% voltage drop.

MCA for 7   Ton 230V unit = 43.3 (from S&R plate).

Applying previous table wire sizes less than #8 AWG 
cannot be used for circuits which have a rating of 45A. 
The #8 wire is not suitable since the maximum length for 
a 45A circuit is 68’. 
Solution: Use a #6 AWG wire suitable up to 110’. 

NOTE: It is the contractors’s responsibility to follow the 
NEC (USA) or CEC (Canada) when sizing the service 
wire for this unit.

½

Local codes often require a disconnect switch located near the
unit; do not install the switch on the unit.  Refer to the installa-
tion instructions supplied with the indoor furnace/air handler for
specific wiring connections and indoor unit configuration.  Like-
wise, consult the instructions packaged with the thermostat
for mounting and location information.

Overcurrent Protection

The following overcurrent protection devices are approved for
use.

Time delay fuses

HACR type circuit breakers

These devices have sufficient time delay to permit the motor-
compressor to start and accelerate its load.

Refer to the unit serial plate and this table for the maximum
overcurrent protection permitted.

Run all line voltage wiring a conduit from the service discon-
nect box to the unit. Refer to the NEC (USA) or CEC (Canada)
codes for the correct size conduit based on the wire size. The
conduit enters the control box through the hole provided in the
bottom. 

NOTE: 

The control box hole is sized for 3/4” conduit. If

permitted by code, a flexible conduit is preferred to minimize
vibration transmission from the unit to the building.

Connect the line voltage wires to the L1, L2, and L3 terminals
of the definite purpose contactor (located in the unit control
box). Refer to the wiring diagram attached to the unit when
making these connections.

Three Phase Compressor Rotation

Use care when handling scroll compressors. Dome temp-
eratures could be hot.

CAUTION

Three phase scrolls are power phase dependent and can com-
press in more than one direction.

Verify proper rotation for three phase compressors by ensuring
the suction pressure drops and discharge pressure rises when
the compressor is energized. 

NOTE: 

 When operated in re-

verse, a three phase scroll compressors is noisier and its cur-
rent draw substantially reduced compared to marked values.

To correct, disconnect power and switch any two leads at the
unit contactor and re-observe.

High Voltage Connections

Route power supply and ground wires through the high voltage
port and terminate in accordance with the wiring diagram pro-
vided inside the control panel cover.

Low Voltage Connections

Condensing unit control wiring requires a two-conductor low
voltage circuit from the room thermostat. The wiring should be
no smaller than 18 AWG and the field connection for this cir-
cuit  must be made in the unit control box using solderless
connectors (i.e. wire nuts). See the following diagram for a
typical low voltage hook-up.

SINGLE STATE LOW VOLTAGE HOOK-UP

YELLOW

BLACK

WHITE

BLUE

BLUE

THERMOSTAT CHT18-60

CONDENSING 

UNIT

CKL090/120

Y1

W1

R

G

AIR 

HANDLER
AH090/120

RED

NOTES:
1). THERMOSTAT TO AIR HANDLER CABLE
MUST HAVE A MINIMUM OF (4) CONDUCTORS

2). AIR HANDLER TO CONDENSING UNIT CABLE
MUST HAVE A MINIMUM OF (2) CONDUCTORS

WIRE NUT

GREEN

System Start Up

Never operate the compressor with the suction valve

 

closed to

test the compressor’s pumping efficiency. In some

 

cases, this

can result in serious compressor damage and loss of warranty
coverage.

NOTICE

THIS UNIT IS SHIPPED WITH A NITROGEN/HELIUM 
HOLDING CHARGE ONLY.  UNIT MUST BE 
EVACUATED AND CHARGED PER INSTALLATION 
INSTRUCTIONS WITH REFRIGERANT LISTED ON 
SERIAL RATING PLATE.

UNITS SHIPPED WITH A HOLDING CHARGE ARE
INTENDED FOR COMPONENT REPLACEMENT 
ONLY ON EXISTING SYSTEMS, AND NOT 
INTENDED FOR USE IN NEW SYSTEMS OR NEWLY
CONSTRUCTED HOMES.

NOTICE

NOTICE

UNITS MUST ONLY BE USED AS REPLACEMENT
COMPONENTS FOR PRE-2010 INSTALLED
SYSTEMS.

Содержание CONDENSING AC UNIT

Страница 1: ...s no responsibility for equip ment installed in violation of any codes or regulations The United States Environmental Protection Agency EPA has issued various regulations regarding the introduc tion and disposal of refrigerants Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines Should you have any questions please contact the local offi...

Страница 2: ...rant used Store cylinders in a cool dry place Never use a cy linder as a platform or a roller Another important consideration in selecting a location for the unit s is the angle to obstructions Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance Corner installations are strongly discouraged 12 12 60 24 Thi...

Страница 3: ... type hanger Keep both lines separate and always insulate the suction line Suct Liq Suct Liq Suct Liq 7 1 2 1 1 8 5 8 1 3 8 5 8 1 3 8 5 8 10 1 3 8 5 8 1 5 8 5 8 1 5 8 5 8 Cond Unit Tons REFRIGERANT LINE LENGTH ft 0 24 25 49 50 74 Line Diameter In OD Full rating line size Lines greater than 74 feet in length or vertical elevation changes more than 50 feet refer to the Remote Cooling Service Manual ...

Страница 4: ...isk of fire or explosion never use oxygen high pressure air or flammable gases for leak testing of a refrigeration system WARNING To avoid possible explosion the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve The pressure relief valve must be set to open at no more than 150 psig WARNING Pressure test the system using dry nitrogen and soapy water to lo...

Страница 5: ... NOTICE Units with reciprocating compressors and non bleed TXV s require a Hard Start Kit This unit is designed for three phase operation DO NOT OP ERATE ON A SINGLE PHASE POWER SUPPLY Measure the power supply to the unit The supply voltage must be in agreement with the unit rating plate power requirements RATED VOLTAGE MINIMUM SUPPLY VOLTAGE MAXIMUM SUPPLY VOLTAGE 208 230V 197 253 460V 414 506 Th...

Страница 6: ...e Compressor Rotation Use care when handling scroll compressors Dome temp eratures could be hot CAUTION Three phase scrolls are power phase dependent and can com press in more than one direction Verify proper rotation for three phase compressors by ensuring the suction pressure drops and discharge pressure rises when the compressor is energized NOTE When operated in re verse a three phase scroll c...

Страница 7: ...p plication should have a subcooling of 11 2 ºF and su perheat of 9 1 ºF a If subcooling and superheat are low adjust TXV to 9 1 ºF superheat then check subcooling NOTE To adjust superheat turn the valve stem clock wise to increase and counter clockwise to decrease b If subcooling is low and superheat is high add charge to raise subcooling to 11 2ºF then check superheat c If subcooling and superhe...

Страница 8: ...oil Clean or replace filters 7 Flash gas in the liquid line 7 Excessive liquid line drop Check liquid line size 8 Quantity of air through evaporator not adequate 8 Increase the blower speed 1 Expansion valve stuck open 1 Correct valve action or replace the valve 2 Expansion valve bulb not in contact with 2 Fasten bulb securely to suction line suction line 3 Suction and or discharge valve leaking o...

Отзывы: