background image

8

TROUBLESHOOTING ANALYSIS TABLE

COMPLAINT

PROBABLE CAUSE

REMEDY

1. Excessive charge of refrigerant in system.

1. Purge or pump-down excessive charge.

2. Inadequate supply of air across the

2. Make certain that coil is not fouled in any

condenser coil.

way, or that air is not re-circulating.

3. Non-condensate gases in the system.

3. Purge these gases from the system.

Recharge system, if necessary.

1. System low on refrigerant.

1. Charge system until sight glass is clear of bubbles.

2. Compressor valves broken.

2. Replace compressor.

1. Liquid line valve closed.

1. Open the liquid line valve.

2. Restricted liquid line.

2. Replace filter-dryer.

3. The bulb of the thermal expansion valve

3. Detach the bulb from the suction line and hold

has lost its charge.

in one hand. If no liquid refrigerant goes through
the valve, replace the valve.

4. System low on refrigerant.

4. Test the unit for leaks. Add refrigerant until sight

glass is free from bubbles, after repairing leak.

5. Dirty filters.

5. Clean or replace filter.

6. Coil frosted up.

6. Defrost and clean coil. Clean or replace filters.

7. Flash gas in the liquid line.

7. Excessive liquid line drop. Check liquid line size.

8. Quantity of air through evaporator not adequate.

8. Increase the blower speed.

1. Expansion valve stuck open.

1. Correct valve action or replace the valve.

2. Expansion valve bulb not in contact with

2. Fasten bulb securely to suction line.

suction line.

3. Suction and/or discharge valve leaking or broken.

3. Replace compressor.

1. Disconnect switch open.

1. Close the disconnect switch.

2. Blow fuse or fuse at disconnect switch.

2. Check the cause of failure and replace the fuse.

3. Thermostat set too high.

3. Adjust to lower temperature.

4. Selector switch in "Off" position.

4. Turn selector switch knob to "Cool" position.

5. Contactor and/or relay coils burned out.

5. Replace contactor and/or relay.

6. Loose or open electrical connection in either

6. Inspect and secure all electrical connections.

the control or power circuit.

5. Compressor will not start.

1. High Head Pressure

2. Low Head Pressure

3. Low Suction Pressure

4. High Suction Pressure

Wiring Diagram

HIGH VOLTAGE!
D

ISCONNECT

 

ALL

 

POWER

 

BEFORE

 

SERVICING

 

OR

 

INSTALLING

 

THIS

 

UNIT

.  

M

ULTIPLE

 

POWER

 

SOURCES

 

MAY

 

BE

 

PRESENT

. F

AILURE

 

TO

 

DO

 

SO

 

MAY

 

CAUSE

 

PROPERTY

 

DAMAGE

PERSONAL

 

INJURY

 

OR

 

DEATH

.

Содержание CONDENSING AC UNIT

Страница 1: ...s no responsibility for equip ment installed in violation of any codes or regulations The United States Environmental Protection Agency EPA has issued various regulations regarding the introduc tion and disposal of refrigerants Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines Should you have any questions please contact the local offi...

Страница 2: ...rant used Store cylinders in a cool dry place Never use a cy linder as a platform or a roller Another important consideration in selecting a location for the unit s is the angle to obstructions Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance Corner installations are strongly discouraged 12 12 60 24 Thi...

Страница 3: ... type hanger Keep both lines separate and always insulate the suction line Suct Liq Suct Liq Suct Liq 7 1 2 1 1 8 5 8 1 3 8 5 8 1 3 8 5 8 10 1 3 8 5 8 1 5 8 5 8 1 5 8 5 8 Cond Unit Tons REFRIGERANT LINE LENGTH ft 0 24 25 49 50 74 Line Diameter In OD Full rating line size Lines greater than 74 feet in length or vertical elevation changes more than 50 feet refer to the Remote Cooling Service Manual ...

Страница 4: ...isk of fire or explosion never use oxygen high pressure air or flammable gases for leak testing of a refrigeration system WARNING To avoid possible explosion the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve The pressure relief valve must be set to open at no more than 150 psig WARNING Pressure test the system using dry nitrogen and soapy water to lo...

Страница 5: ... NOTICE Units with reciprocating compressors and non bleed TXV s require a Hard Start Kit This unit is designed for three phase operation DO NOT OP ERATE ON A SINGLE PHASE POWER SUPPLY Measure the power supply to the unit The supply voltage must be in agreement with the unit rating plate power requirements RATED VOLTAGE MINIMUM SUPPLY VOLTAGE MAXIMUM SUPPLY VOLTAGE 208 230V 197 253 460V 414 506 Th...

Страница 6: ...e Compressor Rotation Use care when handling scroll compressors Dome temp eratures could be hot CAUTION Three phase scrolls are power phase dependent and can com press in more than one direction Verify proper rotation for three phase compressors by ensuring the suction pressure drops and discharge pressure rises when the compressor is energized NOTE When operated in re verse a three phase scroll c...

Страница 7: ...p plication should have a subcooling of 11 2 ºF and su perheat of 9 1 ºF a If subcooling and superheat are low adjust TXV to 9 1 ºF superheat then check subcooling NOTE To adjust superheat turn the valve stem clock wise to increase and counter clockwise to decrease b If subcooling is low and superheat is high add charge to raise subcooling to 11 2ºF then check superheat c If subcooling and superhe...

Страница 8: ...oil Clean or replace filters 7 Flash gas in the liquid line 7 Excessive liquid line drop Check liquid line size 8 Quantity of air through evaporator not adequate 8 Increase the blower speed 1 Expansion valve stuck open 1 Correct valve action or replace the valve 2 Expansion valve bulb not in contact with 2 Fasten bulb securely to suction line suction line 3 Suction and or discharge valve leaking o...

Отзывы: