background image

3

To avoid possible explosion, use only returnable (not
disposable) service cylinders when removing refrig-
erant from a system.
 •  Ensure the cylinder is free of damage which could
    lead to a leak or explosion.
•   Ensure the hydrostatic test date does not exceed
    5 years.
•   Ensure the pressure rating meets or exceeds 400
    lbs.

When in doubt, do not use cylinder.

WARNING

Refrigerant Lines

NOTE: 

For improved refrigerant management, equip the

evaporator coil with a field-supplied thermal expansion valve
(TXV) and the liquid line with a field-supplied liquid line solenoid.
Ensure the solenoid is installed as close as possible to the
evaporator coil to prevent refrigeration migration in the
compressor “OFF” cycle.

Use only refrigerant grade (dehydrated and sealed) copper tub-
ing to connect the condensing unit with the indoor evaporator.
After cutting the tubing, install plugs to keep refrigerant tubing
clean and dry prior to and during installation.  Tubing should
always be cut square keeping ends round and free from burrs.
Clean the tubing to prevent contamination.

Do NOT let refrigerant lines come in direct contact with plumb-
ing, ductwork, floor joists, wall studs, floors, and walls.  When
running refrigerant lines through a foundation or wall, openings
should allow for sound and vibration absorbing material to be
placed or installed between tubing and foundation. Any gap
between foundation or wall and refrigerant lines should be filled
with a pliable silicon-based caulk, RTV or a vibration damping
material. Avoid suspending refrigerant tubing from joists and
studs with rigid wire or straps that would come in contact with
the tubing. Use an insulated or suspension type hanger. Keep
both lines separate and always insulate the suction line.

Suct

Liq

Suct

Liq

Suct

Liq

7 1/2

1 1/8

 5/8

1 3/8

 5/8

1 3/8

 5/8

10

1 3/8

 5/8

1 5/8

 5/8

1 5/8

 5/8

Cond Unit

(Tons)

REFRIGERANT LINE LENGTH (ft)

0-24

25-49*

    50-74**

Line Diameter (In. OD)

* Full rating line size
** Lines greater than 74 feet in length or vertical elevation 
changes more than 50 feet

  refer to the Rem ote Cooling 

Service Manual or contact your distributor for assistance.

Insulation is necessary to prevent condensation from forming
and dropping from the suction line.  Armflex (or satisfactory
equivalent) with 3/8” min. wall thickness is recommended.  In
severe conditions (hot, high humidity areas) 1/2” insulation may
be required.  Insulation must be installed in a manner which
protects tubing from damage and contamination.

Where possible, drain as much residual compressor oil from
existing systems, lines, and traps; pay close attention to low
areas where oil may collect.  

NOTE: 

If changing refrigerant

types, ensure the indoor coil and metering device is compat-
ible with the type of refrigerant being used; otherwise, the in-
door coil must be replaced. To facilitate oil return to the com-
pressor, a horizontal suction line should be pitched (1/2” per
10’ toward the condensing unit.

Filter Drier and Sight Glass

A liquid line filter drier is factory installed. Field-install the sup-
plied sight glass/moisture indicator on the liquid line as close
as practical to the service valve.

Burying Refrigerant Lines

If burying refrigerant lines can not be avoided, use the following
checklist.

1. Insulate liquid and suction lines separately.

2. Enclose all underground portions of the refrigerant lines

in waterproof material (conduit or pipe) sealing the ends
where tubing enters/exits the enclosure.

3. If the lines must pass under or through a concrete slab,

ensure lines are adequately protected and sealed.

Содержание CONDENSING AC UNIT

Страница 1: ...s no responsibility for equip ment installed in violation of any codes or regulations The United States Environmental Protection Agency EPA has issued various regulations regarding the introduc tion and disposal of refrigerants Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines Should you have any questions please contact the local offi...

Страница 2: ...rant used Store cylinders in a cool dry place Never use a cy linder as a platform or a roller Another important consideration in selecting a location for the unit s is the angle to obstructions Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance Corner installations are strongly discouraged 12 12 60 24 Thi...

Страница 3: ... type hanger Keep both lines separate and always insulate the suction line Suct Liq Suct Liq Suct Liq 7 1 2 1 1 8 5 8 1 3 8 5 8 1 3 8 5 8 10 1 3 8 5 8 1 5 8 5 8 1 5 8 5 8 Cond Unit Tons REFRIGERANT LINE LENGTH ft 0 24 25 49 50 74 Line Diameter In OD Full rating line size Lines greater than 74 feet in length or vertical elevation changes more than 50 feet refer to the Remote Cooling Service Manual ...

Страница 4: ...isk of fire or explosion never use oxygen high pressure air or flammable gases for leak testing of a refrigeration system WARNING To avoid possible explosion the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve The pressure relief valve must be set to open at no more than 150 psig WARNING Pressure test the system using dry nitrogen and soapy water to lo...

Страница 5: ... NOTICE Units with reciprocating compressors and non bleed TXV s require a Hard Start Kit This unit is designed for three phase operation DO NOT OP ERATE ON A SINGLE PHASE POWER SUPPLY Measure the power supply to the unit The supply voltage must be in agreement with the unit rating plate power requirements RATED VOLTAGE MINIMUM SUPPLY VOLTAGE MAXIMUM SUPPLY VOLTAGE 208 230V 197 253 460V 414 506 Th...

Страница 6: ...e Compressor Rotation Use care when handling scroll compressors Dome temp eratures could be hot CAUTION Three phase scrolls are power phase dependent and can com press in more than one direction Verify proper rotation for three phase compressors by ensuring the suction pressure drops and discharge pressure rises when the compressor is energized NOTE When operated in re verse a three phase scroll c...

Страница 7: ...p plication should have a subcooling of 11 2 ºF and su perheat of 9 1 ºF a If subcooling and superheat are low adjust TXV to 9 1 ºF superheat then check subcooling NOTE To adjust superheat turn the valve stem clock wise to increase and counter clockwise to decrease b If subcooling is low and superheat is high add charge to raise subcooling to 11 2ºF then check superheat c If subcooling and superhe...

Страница 8: ...oil Clean or replace filters 7 Flash gas in the liquid line 7 Excessive liquid line drop Check liquid line size 8 Quantity of air through evaporator not adequate 8 Increase the blower speed 1 Expansion valve stuck open 1 Correct valve action or replace the valve 2 Expansion valve bulb not in contact with 2 Fasten bulb securely to suction line suction line 3 Suction and or discharge valve leaking o...

Отзывы: