background image

2

Use field-supplied spreader bars when lifting the unit to mini-
mize the possibility of lifting cable/straps damage. To protect
the cabinet louvers, use protective material such as plywood
behind the cable/straps. Arrange the straps to form a central
suspension point. 

NOTE:

 When raising and setting the unit,

observe all safety rules. Remove shipping skid and all protec-
tion and lifting material after the unit is in place.

Safe Refrigerant Handling

While these items will not cover every conceivable situation,
they should serve as a useful guide.

Refrigerants are heavier than air. They can "push out"
the oxygen in your lungs or in any enclosed space.To
avoid possible difficulty in breathing or death:

•  

Never purge refrigerant into an enclosed room or

   space. By law, all refrigerants must be reclaimed.

•  

If an indoor leak is suspected, throughly ventilate the

   area before beginning work.
•  Liquid refrigerant can be very cold. To avoid possible
   frostbite or blindness, avoid contact and wear gloves
   and goggles.  If liquid refrigerant does contact your
   skin or eyes, seek medical help immediately.
•  Always follow EPA regulations. Never burn refrig-
   erant, as poisonous gas will be produced.

WARNING

To avoid possible explosion:
  Never apply flame or steam to a refrigerant cylinder.
    If you must heat a cylinder for faster charging,
    partially immerse it in warm water.

Never fill a cylinder more than 80% full of liquid re-

    frigerant.
•   Never add anything other than R-22 to an R-22 cy-
    linder. The service
    equipment used must be listed or certified for the
    type of refrigerant used.
•   Store cylinders in a cool, dry place. Never use a cy-
    linder as a platform or a roller.

•  

•   

Another important consideration in selecting a location for the
unit(s) is the angle to obstructions.  Either side adjacent the
valves can be placed toward the structure provided the side
away from the structure maintains minimum service clearance.
Corner installations are strongly discouraged.

12"

12"

60"

24"

This unit can be located at ground floor level or on flat roofs. At
ground floor level, the unit must be on a solid, level foundation
that will not shift or settle. To reduce the possibility of sound
transmission, the foundation slab should not be in contact with
or be an integral part of the building foundation. The foundation
slab should be a minimum of 6” wider than the unit in all direc-
tions. Ensure the foundation is sufficient to support the unit. A
concrete slab raised above ground level provides a suitable
base.

The selected site should be no greater than 50’ below or 70’
above the evaporator section. For optimum performance, the
minimum length interconnecting tubing is preferred. When pos-
sible minimize the amount of bends and turns.

Rooftop Installations

If it is necessary to install this unit on a roof structure, ensure
the roof structure can support the weight and that proper con-
sideration is given to the weather-tight integrity of the roof. Since
the unit can vibrate during operation, sound vibration transmis-
sion should be considered when installing the unit. Vibration
absorbing pads or springs can be installed between the con-
densing unit legs or frame and the roof mounting assembly to
reduce noise vibration.

Rigging

To avoid possible injury or death, all panels must be 
in position and secured before lifting this equipment

Содержание CONDENSING AC UNIT

Страница 1: ...s no responsibility for equip ment installed in violation of any codes or regulations The United States Environmental Protection Agency EPA has issued various regulations regarding the introduc tion and disposal of refrigerants Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines Should you have any questions please contact the local offi...

Страница 2: ...rant used Store cylinders in a cool dry place Never use a cy linder as a platform or a roller Another important consideration in selecting a location for the unit s is the angle to obstructions Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance Corner installations are strongly discouraged 12 12 60 24 Thi...

Страница 3: ... type hanger Keep both lines separate and always insulate the suction line Suct Liq Suct Liq Suct Liq 7 1 2 1 1 8 5 8 1 3 8 5 8 1 3 8 5 8 10 1 3 8 5 8 1 5 8 5 8 1 5 8 5 8 Cond Unit Tons REFRIGERANT LINE LENGTH ft 0 24 25 49 50 74 Line Diameter In OD Full rating line size Lines greater than 74 feet in length or vertical elevation changes more than 50 feet refer to the Remote Cooling Service Manual ...

Страница 4: ...isk of fire or explosion never use oxygen high pressure air or flammable gases for leak testing of a refrigeration system WARNING To avoid possible explosion the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve The pressure relief valve must be set to open at no more than 150 psig WARNING Pressure test the system using dry nitrogen and soapy water to lo...

Страница 5: ... NOTICE Units with reciprocating compressors and non bleed TXV s require a Hard Start Kit This unit is designed for three phase operation DO NOT OP ERATE ON A SINGLE PHASE POWER SUPPLY Measure the power supply to the unit The supply voltage must be in agreement with the unit rating plate power requirements RATED VOLTAGE MINIMUM SUPPLY VOLTAGE MAXIMUM SUPPLY VOLTAGE 208 230V 197 253 460V 414 506 Th...

Страница 6: ...e Compressor Rotation Use care when handling scroll compressors Dome temp eratures could be hot CAUTION Three phase scrolls are power phase dependent and can com press in more than one direction Verify proper rotation for three phase compressors by ensuring the suction pressure drops and discharge pressure rises when the compressor is energized NOTE When operated in re verse a three phase scroll c...

Страница 7: ...p plication should have a subcooling of 11 2 ºF and su perheat of 9 1 ºF a If subcooling and superheat are low adjust TXV to 9 1 ºF superheat then check subcooling NOTE To adjust superheat turn the valve stem clock wise to increase and counter clockwise to decrease b If subcooling is low and superheat is high add charge to raise subcooling to 11 2ºF then check superheat c If subcooling and superhe...

Страница 8: ...oil Clean or replace filters 7 Flash gas in the liquid line 7 Excessive liquid line drop Check liquid line size 8 Quantity of air through evaporator not adequate 8 Increase the blower speed 1 Expansion valve stuck open 1 Correct valve action or replace the valve 2 Expansion valve bulb not in contact with 2 Fasten bulb securely to suction line suction line 3 Suction and or discharge valve leaking o...

Отзывы: