Overfill prevention divice type BC-1
14 / 16
TECHNICAL DATA
Indicator
Supply voltage
230V AC; 50-60Hz
Power consumption
4.5VA
Voltage tolerance
+10% / -15%
Protection type
IP30 or IP65 acc. to EN 60529
Housing
PE or PC
Dimensions H x W x D
Type BC-1-1
200 x 120 x 58mm
Type BC-1-2
225 x 138 x 80mm
Type BC-1-4
120 x 120 x 49mm
Sound level of alarm sound:
≥
70dB(A)
Probe
Voltage:
12V DC
Probe length
Z = 150 to 1000mm
Length of the probe connection
cable
Standard
Materials
1.4301 ; 1.405 ; PA (depending on the version)
Installation position:
vertically upright
Diameter of the probe tube
10mm
Diameter of sensor cover
18mm
Temperature of the operating
media
-20°C to +60°C
Ambient temperature
-20°C to +60°C
The BC-1 is a regulating and control system (RS) of over-voltage category III,
contamination degree 2 according to EN 60730-1.
Protection class type 2
WARRANTY
We guarantee that the product will function as intended and will not leak during
the legally specified period. The scope of our warranty is based on Section 8 of
our terms and conditions of delivery and payment.
TECHNICAL CHANGES
All the information contained in this assembly and operating manual is the result of product
testing and corresponds to the level of knowledge at the time of testing and the relevant
legislation and standards at the time of issue. We reserve the right to make technical changes
without prior notice. Errors and omissions excepted. All figures are for illustration purposes
only and may differ from actual designs.