- 5 A SIL 3 NC contact Relay Out Module for NE or F&G/ND Load with full diagnostic and Modbus  G.M. International ISM0222-9 

PPC5092 Adapter - Operation 

 The Pocket Portable Adapter type PPC5092 is suitable to connect the module D5295S to a PC via USB serial line, in order to configure and to monitor the operation parameters 
by means of SWC5090 software. The PPC5092 unit is connected to D5295S by mini USB and to PC by USB port. This adapter is not ATEX, UL or FM approved and is only to be used 
in Safe Area/Non Hazardous Locations. Do not use PPC5092 in Hazardous Area/Hazardous Locations. The PPC5092 adapter is powered by the PC (no battery power) when its USB 
port is plugged into the PC. It has a green LED as power-on indication. 

SWC5090 Configuration & Monitoring Software 

 

USER MANUAL SETTINGS: 

Allowed ranges of the field parameters. 

Load Supply Voltage RMS 

 Voltage Upper Limit (V): Maximum allowed load RMS voltage 

 Voltage Lower Limit (V): Minimum allowed load RMS voltage  

Load Current RMS 

 Current Upper Limit (A): Maximum allowed load RMS current 

 Current Lower Limit (A): Minimum allowed load RMS current 

Load OFF Resistance 

 Resistance Upper Limit (

): Maximum allowed load OFF resistance 

 Resistance Lower Limit (

): Minimum allowed load OFF resistance 

Isolation Resistance 

 Resistance Lower Limit (k

): Minimum allowed load-to-earth isolation resistance 

FAULT CONDITIONS MONITORING (Command Status [ON]):

 Faults contributing to the 

output cumulative fault when the driver is on. 



Load Supply Voltage: When checked, the load supply voltage can activate the 
cumulative fault. 



Coil Integrity: When checked, the short circuit of any coil can activate the cumulative 
fault. 



Load OFF Resistance: When checked, the load OFF resistance can activate the 
cumulative fault. 



Isolation Resistance: When checked, the load-to-earth isolation resistance can 
activate the cumulative fault. 

FAULT CONDITIONS MONITORING (Command Status [OFF]):

 Faults contributing to 

the output cumulative fault when the driver is off. 



Load Supply Voltage: When checked, the load supply voltage can activate the 
cumulative fault. 



Load Current: When checked, the load current can activate the cumulative fault. 

TAG: 

Identification of the specific operating loop of the module. 

ACQUIRE FUNCTIONS: 

Acquisition and saving of the diagnostics field parameters. 



Acquire OFF parameters: The currently measured OFF parameters are copied to the 
USER MANUAL SETTINGS (available only when the driver is OFF). 



Acquire ON parameters: The currently measured ON parameters are copied to the 
USER MANUAL SETTINGS (available only when the driver is ON). 

CONTINUOUS SCAN: 

Continuous measurement of the field parameters. 



Start/Stop: Activates/de-activates the measurement of the field parameters. 

INVERT FAULT RELAY: 

When not checked, the output fault contacts open in case of 

fault. When checked, the output fault contacts close in case of fault. 
For SIL application, this field must NOT be checked. 

Note: For advanced options and details on SWC5090, please refer to ISM0154. 

Configuration 

Monitor 

Configuration parameters: 

Screenshots: 

Содержание D5295S

Страница 1: ...E or F G ND Load with full diagnostic and Modbus G M International ISM0222 9 5 A SIL 3 NC contact Relay Output Module for NE or F G ND Load with full diagnostic and Modbus DIN Rail Power Bus and Termination Board Model D5295S D5295S INSTRUCTION MANUAL ...

Страница 2: ... on 28 02 2014 valid for 20 years Mounting EN IEC60715 TH 35 DIN Rail with or without Power Bus or on customized Termination Board Weight about 235 g Connection by polarized plug in disconnect screw terminal blocks to accommodate terminations up to 2 5 mm2 Location installation in Safe Area Non Hazardous Locations or Zone 2 Group IIC T4 or Class I Division 2 Group A B C D T4 or Class I Zone 2 Grou...

Страница 3: ...ergized load condition 5 A high availability SIL 3 contacts for NE or F G ND load 6 A inrush current at 24 Vdc 250 Vac Input Output Supply isolation EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety system ATEX IECEx UL C UL UKR TR n 898 TÜV Certifications FM FMC EAC EX Certifications pending TÜV Functional Safety Certification Simplified installation using standard DIN...

Страница 4: ...rotection fuse or similar chosen according to the relay breaking capacity diagram All relay contacts are shown in de energized position MODEL D5295S 15 16 13 Load Power DC AC 11 12 1 2 9 10 3 4 14 SIL 3 Out 21 Power and Fault Bus F Modbus RS485 for diagnostic A B Load and Line Diagnostic Supply 24 Vdc In Fault Out 2 250 V 3 A A B MODBUS IN OUT RS485 Fault Out 1 30 V 500 mA Termination board connec...

Страница 5: ...ith the effective operating environment of the specific installation Units must be protected against dirt dust extreme mechanical e g vibration impact and shock and thermal stress and casual contacts If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water Electrostatic Hazard to avoid electrostatic hazard the enclosure of D5295S must be cleaned only w...

Страница 6: ...put cumulative fault when the driver is on Load Supply Voltage When checked the load supply voltage can activate the cumulative fault Coil Integrity When checked the short circuit of any coil can activate the cumulative fault Load OFF Resistance When checked the load OFF resistance can activate the cumulative fault Isolation Resistance When checked the load to earth isolation resistance can activa...

Страница 7: ...e Bit position 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Coil Integrity Load Current Load Voltage 0 Ok 1 Fault Each Modbus parameter is described by one 16 bit word 1 See command details on the right 2 Expressed in 100 mV 3 Expressed in mA 4 Expressed in Ω 5 Expressed in kΩ 6 0 OFF 1 ON 7 0 Fault 1 Ok 8 0 Fault mirror 1 Always OFF 2 Always ON 9 0 no inversion open fault for SIL application 1 inverted ...

Отзывы: