D5295 

- 45A SIL 3 NC contact Relay Out Module for NE or F&G/ND Load with full diagnostic and Modbus 

G.M. International ISM0222-9 

Supported ModBus Parameters

 

Param.  

Address 

Description 

Notes 

G.M. Factory Code 

Identification 

Data  

Instrument Code 

Option Code 

Hardware Release 

Software Release 

16 

Modbus Address 

Communication 

Data 

17 

Modbus Baudrate

(1)

 

18 

Modbus Format

(1)

 

64 

Measured Load Voltage 

(2)

 

Input Data   

65 

Measured Load Current 

(3)

 

69 

Driver Status 

(6)

 

70 

Coil Integrity 

(7)

 

72 

Masked Fault Status

(1)

 

101 

Load Voltage Upper Limit 

(2)

 

Input 

Configuration   

102 

Load Voltage Lower Limit 

(2)

 

103 

Load Current Upper Limit 

(3)

 

104 

Load Current Lower Limit 

(3)

 

112 

Fault Mirror Configuration 

(8)

 

113 

Invert Fault Relay 

(9)

 

114 

Load Voltage Upper Hysteresis 

(2)

 

115 

Load Voltage Lower Hysteresis 

(2)

 

116 

Load Current Upper Hysteresis 

(3)

 

117 

Load Current Lower Hysteresis 

(3)

 

224 

Fault Mask (Driver ON)  

Fault  

Conditions 

225 

Fault Mask (Driver OFF)  

464 

Command execution

(10)

 

Command  

548 to 555  Tag

(11)

 

Tags  

Type

(12)

 

R/W 

R/W 

R/W 

R/W 

105 

Load Resistance Upper Limit (Low 16 bits) 

(4)

 

106 

Load Resistance Upper Limit (High 16 bits) 

107 

Load Resistance Lower Limit (Low 16 bits) 

(4)

 

109 

Isolation Resistance Lower Limit 

(5)

 

108 

Load Resistance Lower Limit (High 16 bits) 

120 

Isolation Resistance Hysteresis 

(5)

 

118 

Load Resistance Upper Hysteresis 

(4)

 

119 

Load Resistance Lower Hysteresis 

(4)

 

66 

Measured Load Resistance (Low 16 bits) 

(4)

 

68 

Measured Isolation Resistance 

(5)

 

67 

Measured Load Resistance (High 16 bits)  

Index 

Baudrate 

0 4800 
1 9600 
2 19200 
3 38400 
4 57600 
5 115200 

Address 17: Supported ModBus Baudrates  

Address 72: Fault status 

High Byte

 

Low Byte 

Bit position 

15  14  13  12  11  10  9  8  7  6  5 4 3 2 1 0 

Coil Integrity 

Load Current  

Load Voltage  

0= Ok 
1= Fault 

Each Modbus parameter is described by one 16-bit word. 
 
(1) See command details on the right. 
(2) Expressed in 100 mV 
(3) Expressed in mA 
(4) Expressed in 

 

(5) Expressed in k

 

(6) 0= OFF; 1= ON 
(7) 0= Fault; 1= Ok 
(8) 0= Fault mirror; 1= Always OFF; 2= Always ON 
(9) 0= no inversion (open: fault, for SIL application); 1= inverted (open: ok) 
(10) All configurations must be confirmed via Addr. 464, see details on the right. 
(11) Tags are composed of 16 characters. 

    Each address contains 2 chars, starting from left. 

(12) Parameter Type: 
   

R= read only 

   

W= write only 

   

R/W= read and write 

Address 464: Commands 

High Byte 

Low Byte 

Bit position 

15  14  13  12  11  10  9  8  7  6  5  4 3 2 1 0 

1 Save Input/Output Configuration 

2 Save Modbus Configuration 

8 Save Tags 

Address 18: Supported Modbus Formats

 

High Byte 

Low Byte 

Bit position 

15  14  13  12  11  10  9  8  7  6  5  4 3 2 1 0 

Termination resistance (1 = enabled) 

Endianness 32 bit Data (0 = Little; 1 = Big) 

Supported Modbus Parity: 
0 8 data bit, no parity, 1 stop bit 
1 8 data bit, even parity, 1 stop bit 
2 8 data bit, odd parity, 1 stop bit 

Isolation Resistance 

Load Resistance 

Addresses 224-225: Fault conditions 

High Byte

 

Low Byte 

Bit position 

15  14  13  12  11  10  9  8  7  6  5 4 3 2 1 0 

Coil Integrity 

Load Current  

Load Voltage  

0= Ok 
1= Fault 

Isolation Resistance 

Load Resistance 

Configuration Parameters: 

Configuration parameters: 

Code 

Name 

Notes 

03 

read holding registers 

reads a stream of words from memory 

04 

read input registers 

reads a stream of words from memory 

08 

diagnostics: subcode 0 

returns query data 

06 write 

single 

registers  writes a word in memory 

16 

write multiple registers 

writes a stream of words in memory 

D5295S communicates via Modbus RTU-485 protocol. Below are all available registers. 

Parameters Details:

 

Содержание D5295S

Страница 1: ...E or F G ND Load with full diagnostic and Modbus G M International ISM0222 9 5 A SIL 3 NC contact Relay Output Module for NE or F G ND Load with full diagnostic and Modbus DIN Rail Power Bus and Termination Board Model D5295S D5295S INSTRUCTION MANUAL ...

Страница 2: ... on 28 02 2014 valid for 20 years Mounting EN IEC60715 TH 35 DIN Rail with or without Power Bus or on customized Termination Board Weight about 235 g Connection by polarized plug in disconnect screw terminal blocks to accommodate terminations up to 2 5 mm2 Location installation in Safe Area Non Hazardous Locations or Zone 2 Group IIC T4 or Class I Division 2 Group A B C D T4 or Class I Zone 2 Grou...

Страница 3: ...ergized load condition 5 A high availability SIL 3 contacts for NE or F G ND load 6 A inrush current at 24 Vdc 250 Vac Input Output Supply isolation EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety system ATEX IECEx UL C UL UKR TR n 898 TÜV Certifications FM FMC EAC EX Certifications pending TÜV Functional Safety Certification Simplified installation using standard DIN...

Страница 4: ...rotection fuse or similar chosen according to the relay breaking capacity diagram All relay contacts are shown in de energized position MODEL D5295S 15 16 13 Load Power DC AC 11 12 1 2 9 10 3 4 14 SIL 3 Out 21 Power and Fault Bus F Modbus RS485 for diagnostic A B Load and Line Diagnostic Supply 24 Vdc In Fault Out 2 250 V 3 A A B MODBUS IN OUT RS485 Fault Out 1 30 V 500 mA Termination board connec...

Страница 5: ...ith the effective operating environment of the specific installation Units must be protected against dirt dust extreme mechanical e g vibration impact and shock and thermal stress and casual contacts If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water Electrostatic Hazard to avoid electrostatic hazard the enclosure of D5295S must be cleaned only w...

Страница 6: ...put cumulative fault when the driver is on Load Supply Voltage When checked the load supply voltage can activate the cumulative fault Coil Integrity When checked the short circuit of any coil can activate the cumulative fault Load OFF Resistance When checked the load OFF resistance can activate the cumulative fault Isolation Resistance When checked the load to earth isolation resistance can activa...

Страница 7: ...e Bit position 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Coil Integrity Load Current Load Voltage 0 Ok 1 Fault Each Modbus parameter is described by one 16 bit word 1 See command details on the right 2 Expressed in 100 mV 3 Expressed in mA 4 Expressed in Ω 5 Expressed in kΩ 6 0 OFF 1 ON 7 0 Fault 1 Ok 8 0 Fault mirror 1 Always OFF 2 Always ON 9 0 no inversion open fault for SIL application 1 inverted ...

Отзывы: