background image

 

D5295 

- 45A SIL 3 NC contact Relay Out Module for NE or F&G/ND Load with full diagnostic and Modbus 

G.M. International ISM0222-9 

 

Warning 

Operation 

 The single channel 5 A Relay Output D5295S is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed.2 for high risk 
industries. It provides isolation between input and output contacts. D5295S has 2+2 SPST relay contacts connected in parallel and then in series to avoid spurious trip and to increase 
availability (see function diagram). High availability SIL 3 Safety Function for NE load or F&G/ND load is available at Terminal Blocks 13-14. When the driving signal is high (24 Vdc), the 
relay is energized, contacts at terminals 13-15 and 14-16 are open and load is de-energized. When the driving signal is low (0 Vdc), the relay is de-energized, contacts at terminals  
13-15 and 14-16 are closed and the load is energized. Presence of diagnostic circuit power supply, status of input / output channel (energized or de-energized), as well as any type of 
fault condition (line and load short/open circuit, relay coil short circuit, etc.) are displayed by related signalling LEDs: green power supply, yellow for status channel and red for fault. 

Installation 

 D5295S is a relay output module housed in a plastic enclosure suitable for installation on EN/IEC60715 TH 35 DIN-Rail, with or without Power Bus or on customized Termination 
Board. D5295S unit can be mounted with any orientation over the entire ambient temperature range. Electrical connection of conductors up to 2.5 mm² are accommodated by polarized 
plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage 

(for Zone 2 installations check the area to be 

nonhazardous before servicing). 

The wiring cables have to be proportionate in base to the current and the length of the cable. On the section “Function Diagram” and enclosure side a 

block diagram identifies all connections. Identify the function and location of each connection terminal using the wiring diagram on the corresponding section, as an example: 
Connect 24 Vdc power supply positive at terminal “9” and negative at terminal “10”. 
Connect positive input at terminal “1” and negative input at “2”. 
Connect Fault output 1 (30 V, 500mA) at terminals “3” and “4” and Fault output 2 (250 V, 3A) at terminals “11” and “12”. 
Connect A- Modbus RS845 for diagnostic at terminal “5” and B+ at terminal “6”. 
Connect positive output NE or F&G/ND load at terminal “13” and  negative at terminal “14”. 
Connect positive Load Power DC/AC at terminal “15” and negative at terminal “16”. 
Connect ground at terminal “21”.  
Installation and wiring must be in accordance to the relevant national or international installation standards (e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres 
Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection. 
Connect 2+2 SPST relay contacts checking the load rating to be within the contact maximum rating 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load). 

To prevent relay con-

tacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram on data sheet. 

The enclosure provides, 

according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation requires an additional 
enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. Units must be protected 
against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a cloth lightly moistened by a 
mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5295S must be cleaned only with a damp or antistatic cloth. 

Any penetration 

of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. According to EN61010, D5295 must be connected to SELV or 
SELV-E supplies. Relay output contact must be connected to load non exceeding category II overvoltage limits. 

Warning: de-energize main power source (turn off power supply 

voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live hazardous potential. 

 

 

D5295S is an electrical apparatus installed into EN/IEC60715 TH 35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature Classification T4, Hazardous Area 
(according to EN/IEC60079-15) within the specified operating temperature limits Tamb - 40 to +70 °C. D5295S must be installed, operated and maintained only by qualified personnel, in 
accordance to the relevant national/international installation standards (e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in 
hazardous areas (other than mines)), following the established installation rules. De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks 
when installed in Hazardous Area or unless area is known to be nonhazardous. 

Warning: substitution of components may impair suitability for Zone 2. Warning: de-energize 

main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock when connected to live 
hazardous potential

Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be  

onhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be  

returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

Start-up 

 Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires. Check conductors for exposed wires that 
could touch each other causing dangerous unwanted shorts. Turn on power for diagnostic circuit, the “power on” green led must be lit. Enabling input, the channel status yellow led must 
be lit and load circuit must be de-energized because 2+2 SPST relay output contacts are open. Instead, disabling input, the channel status yellow led must be turned off and load circuit 
must be energized because 2+2 SPST relay output contacts are closed. 

Configuration during T-proof testing for functional safety relay and diagnostic applications 

For configuration of T-proof relays and diagnostic circuits testing, some DIP Switches are located on component side of pcb. These switches allow the T-proof relays and diagnostic 
circuits test (SW1 dip-switch: 1-2-3-4 set “ON” and see “Testing procedure at T-proof for functional safety relay and diagnostic applications” on ISM0442 Safety Manual). 

WARNING: 

after T-proof test, dip-switch 1-2-3-4 must be set 
to “OFF” position for normal operation. 

SW1 Dip switch configuration 

1

2

3

4

ON

T-proof relays enable

1

2

3

1

2

3

Normal Operation

ON ON

OFF

ON

OFF

OFF

T-proof relays (dip1 = relay1;

dip2 = relay2; dip3 = relay3;

dip4 = relay4)

4

OFF

ON

4

This is factory settings 

Содержание D5295S

Страница 1: ...E or F G ND Load with full diagnostic and Modbus G M International ISM0222 9 5 A SIL 3 NC contact Relay Output Module for NE or F G ND Load with full diagnostic and Modbus DIN Rail Power Bus and Termination Board Model D5295S D5295S INSTRUCTION MANUAL ...

Страница 2: ... on 28 02 2014 valid for 20 years Mounting EN IEC60715 TH 35 DIN Rail with or without Power Bus or on customized Termination Board Weight about 235 g Connection by polarized plug in disconnect screw terminal blocks to accommodate terminations up to 2 5 mm2 Location installation in Safe Area Non Hazardous Locations or Zone 2 Group IIC T4 or Class I Division 2 Group A B C D T4 or Class I Zone 2 Grou...

Страница 3: ...ergized load condition 5 A high availability SIL 3 contacts for NE or F G ND load 6 A inrush current at 24 Vdc 250 Vac Input Output Supply isolation EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety system ATEX IECEx UL C UL UKR TR n 898 TÜV Certifications FM FMC EAC EX Certifications pending TÜV Functional Safety Certification Simplified installation using standard DIN...

Страница 4: ...rotection fuse or similar chosen according to the relay breaking capacity diagram All relay contacts are shown in de energized position MODEL D5295S 15 16 13 Load Power DC AC 11 12 1 2 9 10 3 4 14 SIL 3 Out 21 Power and Fault Bus F Modbus RS485 for diagnostic A B Load and Line Diagnostic Supply 24 Vdc In Fault Out 2 250 V 3 A A B MODBUS IN OUT RS485 Fault Out 1 30 V 500 mA Termination board connec...

Страница 5: ...ith the effective operating environment of the specific installation Units must be protected against dirt dust extreme mechanical e g vibration impact and shock and thermal stress and casual contacts If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water Electrostatic Hazard to avoid electrostatic hazard the enclosure of D5295S must be cleaned only w...

Страница 6: ...put cumulative fault when the driver is on Load Supply Voltage When checked the load supply voltage can activate the cumulative fault Coil Integrity When checked the short circuit of any coil can activate the cumulative fault Load OFF Resistance When checked the load OFF resistance can activate the cumulative fault Isolation Resistance When checked the load to earth isolation resistance can activa...

Страница 7: ...e Bit position 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Coil Integrity Load Current Load Voltage 0 Ok 1 Fault Each Modbus parameter is described by one 16 bit word 1 See command details on the right 2 Expressed in 100 mV 3 Expressed in mA 4 Expressed in Ω 5 Expressed in kΩ 6 0 OFF 1 ON 7 0 Fault 1 Ok 8 0 Fault mirror 1 Always OFF 2 Always ON 9 0 no inversion open fault for SIL application 1 inverted ...

Отзывы: