Global Mainstream Dynamic Energy Technology Ltd.
- 31 -
User Manual
Powervortex 5200TL hybrid inverter
to 03 when Powervortex 4600TL / 5200TL PV1 and PV2 ports are connecting with different PV
strings respectively. The CNY should be set to 04 when Powervortex 4600TL / 5200TL PV1 and PV2
ports are connecting with same PV string.
The system default value is 03, please press”OK”to modify it. Press “OK” to finish this setting and
you will enter the setting interface as shown in Figure .
Note:This setting should be operated when the Powervortex 4600TL / 5200TL is under ”wait”
status,otherwise“E05” Error might occur.
4.1.5.10 Setting Operation Mode
Figure 30 Operation mode setting
MDE refers to operation mode. The MDE code 00refers to self-use mode, 01 refers to time-of-use
mode. The default value is 00 and press “OK” to modify it.
If modify MDE value into 01 as shown in Figure , press “OK” the system will enter the charging
time range setting interface as shown in Figure . For example, if you want the system start to
charge the battery at 22.00 and stop charging at 5.00 next morning, then please set the digits
on Figure as “22:00”, “05:00” respectively. The charging current is the same as the Ic that has
been set in Section 4.1.5.7.
Press “OK” to enter into the discharging time range setting interface as shown in Figure 30. Like
setting the charging time range as above, if to discharge the battery from 8am to 5pm(17:00)
every day, then please set the digits on Figure 30 as “08:00”,”17:00” . The discharging current is
the same as the Id current that has been set in 4.1.5.6.