Global Mainstream Dynamic Energy Technology Ltd.
- 14 -
User Manual
Powervortex 5200TL hybrid inverter
Powervortex4600TL / 5200TL
DC
DC
DC
DC
DC
AC
PV1
PV2
GRID
LOAD
K-battery
BAT
S
E
T
Si
ng
le
E
ne
rg
y
Me
te
r
L
N
L
’
N
’
5
6
7
8
K-inv
Grid
K-load
Meter
K-el
Emergency Load
Load
Figure 4 Recommended system configuration
One AC breaker, K-inv, should be installed between the inverter and the AC grid.
An external DC breaker K-battery (or fuse) should be installed between battery packs and
Powervortex 4600 / 5200TL.
Installation:
1. Please read the user manual carefully and pay special attention to the safety rules.
2. Unpack and install the inverter according to section 3.2 and section 3.3.
3. Connect PV wiring according to section 3.4.2.
4. Connect battery wiring according to section 3.4.2.
5. Connect AC wiring (Load/Grid) according to section 3.4.3.
CAUTION
Battery interface must be connected and locked when the system
running.
CAUTION
An over current protection device is needed for all the DC inputs
Setting:
1. Switching on the DC switch for Powervortex4600TL /5200TL, the LCD is lighting now
2. Configure battery packs parameters and system running mode (Self-use default, peak
shaving optional) via integrated LCD. For details, please refer to the operation guide of the LCD
description in Section 4
3. Switching off the DC switch (for saving the parameters).
Starting:
4. Turn on AC Breaker K-inv at grid side
5. Switch on DC switch of hybrid inverter
6. Turn on DC Breaker K-battery at battery side
The inverter is now ready for automatic operation
Disconnecting for maintenance:
1. Turn off DC Breaker D1 at battery side