Powervortex 5200TL hybrid inverter
battery types.
Press “OK” to modify setting on this parameter. Make sure the BVH value input here is higher
than the BVL value set in Section 4.1.5.5. Press “OK” to finish this setting and you will enter the
setting interface as shown in Figure .
4.1.5.5 Setting Battery Discharging Cut-off Voltage
Figure 25 discharging cut-off voltage setting
BVL refers to battery discharging cut-off voltage with setting range from 40V to 60V. Default BVL
value is 46V for lithium battery and 47V for lead-acid battery. Please set the voltage according
to the battery recommended value for different battery types.
Press “OK” to modify the value and please make sure the BVL value input is smaller than the BVH
value in 4.1.5.4. Press “OK” to finish this setting and you will enter the setting interface as shown in
Figure .