8-5-3 Installation Status
This function will show the status of the network and error messages. Example: “No nodes detected”.
8-5-4 Broadcast Configuration
This function will send the local configuration to all panels in the system.
NOTE:
●
Before running this configuration, ensure that the latest configuration is already uploaded into the panel.
●
Before running this function, please go to each panel in the network and run on each one the 8-5-2 - menu and
verify that all panels are “seeing” each other and there are no communication issues.
●
Do not unplug the power during Broadcast.
●
Do not run this function if you have network issues.
●
Ensure that the firmware is the same in all panels.
8-5-5 Communication Channels
This function shows which channels are receiving info from the network.
If the panel has previously received data on a specific channel and no longer listens to messages, meaning that the
channel lost the receiving data, then it will signal (ERR).
NOTE:
Chameleon Communications faults are focused on the lack of “listening/receiving” path. Most of the
communications faults are detected by loss on a normally receiving channel. The Chameleon Communications do not
validate bidirectional communication, but only the missing reception point of view.
8-5-6 BMS Setup
This function will configure all Building Management System (BMS) Protocols available. . The programmable channels in
the NODE are CH1, CH2 and CH3. BMS Protocols can be individually programmed per channel.
The Chameleon Panels support the following BMS configuration in each of the CHANNELS:
BMS
PANEL ADDRESS
PROTOCOL
SELECTION
TYPE
SPECIFIC
comments
XX (not applied)
NONE
(not applied)
working as a normal Chameleon port
XX (not applied)
UI
(not applied
working with MIMIC module or CHAMELEON DISPLAY
XX (not applied)
PRINTER
(not applied
Working with external PRINTER
01-64
MODBUS-RTU
(not applied)
working as an MODBUS port
=> with the specified PANEL ADDRESS
01 to 64
ODYSSEY
(not applied)
working as an Odyssey port
=> with the specified PANEL ADDRESS
XX
(not applied)
SHORT MSG
1
working as “short text” serial port
=> DECT, no fault
('B'-Alarm / 'V'-PreAlarm)
2
working as “short text” serial port
=> DECT, transmit faults
('B'-Alarm / 'V'-PreAlarm / F-Faults)
3
working as “short text” serial port
=> SafeTel, no faults
('Al'-Alarm / 'Fo'-PreAlarm)
4
working as “short text” serial port
=> SafeTel, transmit faults
('Al'-Alarm / 'Fo'-PreAlarm / 'De'-Device Faults / 'Sy'-System Faults)
NODE+ / Installation & Commission Manual / © GFE 220331
42