NODE+ PCB (Main Board)
A
Loop connections. A1 corresponds to Loop 1, A2 to Loop 2, A3 to Loop 3 and A4 to Loop 4
B
Direct Communication to UI Front-End PCB
C
Communication channel: CH1, CH2 and CH3 (BMS)
D
USB Connector (Micro-USB type B – female)
E
LED NODE connection (Used on the NODE+ product)
F
System power input
G
24 V battery connection
H
Auxiliary change-over relay output 1 (Activated by any fire present on the system, disabled by front button)
I
Auxiliary change-over relay output 2 (Activated by any fire present on the system, disabled by front button)
J
Fault NC relay contact (Activated by any fault present on the system, opens on fault)
K
REM1 configurable input (Remote Evacuation, disable selected detectors, disabled, user access, class change)
L
REM2 configurable input (Remote Evacuation, disable selected detectors, disabled, user access, class change)
M
Fault Path. Switch ON (28 V) by any fault present on the system
N
Fire Path. Switch ON (28 V) by any fire present on the system
O
Switched 24 V auxiliary power supply (switches off, for 15 seconds @ every reset event)
P
24 V auxiliary power supply output for powering external devices. Max 300 mA power limited and monitored
Q
Conventional sounder. Q1 corresponds to Circuit 1 and Q2 corresponds to Circuit 2
R
Earth connection
S
D.I.L. Switch used to configure the panel’s address.
D.I.L. SWITCHES
NODE+ / Installation & Commission Manual / © GFE 220331