KEYS TO USE WITHIN FUNCTIONS
Most functions use some or all of the following keys:
1
▲
and 3
▼
Used to browse through items.
2
►
Often used to change fields (move the cursor). It will also be used
when required to scroll through loops.
ENTER
Used to select items and store changes.
ESC
Used to abort changes and exit.
The cursor is often shown to highlight the item that is being changed.
Help
Where possible, help is displayed automatically and testing aided closely by this manual.
General
Because of the flexibility and functionality of this panel, sometimes it can be quite hard to establish the desired
configuration. Zone, device and group events interact as do the various timers.
If the system does not seem to operate as intended, please take your time and review the various sections in this manual.
Some settings need the front panel buttons to be activated, whilst others can be inhibited for specific devices.
The basic functionality of the panel is readily available and the fire alarm system will be operational just by supplying it
with electrical power. Exercising cause and effect capability is what this section is all about. The best way to become
familiar with all the programming facilities of this panel will be a hands-on approach, by creating a step-by-step
configuration.
PROGRAMING FUNCTIONS DESCRIPTION
1 Review Historic Log
All the functions associated with reviewing or printing events and settings.
1-1 Display Historic Log
The panel logs all events in an internal event log. It can store a rolling 10000 entries. When it is full, the latest entry is
added and the oldest entry discarded.
Help is automatically displayed on entry to the function, because it is not possible to display a log entry and help at the
same time. To select a specific entry, input the number and then press ENTER.
1-3 Clear Historic Log
Clears the Historic Log. Only if logged in with Master access code.
1-5 Read/Clear Autostart Count
Every time the Panel's power is cycled, the Autostart count is incremented. SYSTEM RESETs from the front panel button do
not increment the Autostart count.
3 Zones - Disable & Assign
All the functions associated with managing Zones
3-1 Disable Zones
Allows you to disable or enable Zones.
All devices in disabled Zones will cease to operate with the exception of the (audible) output from loop sounders.
Any Zones that are disabled will also be indicated when programming mode is exited. They can then be reviewed using
the DISABLED (QUEUE REVIEW) button.
3-2 Assign Sounder Groups to Zones
Sounder Groups (set up using the Sounders programming functions) can be assigned to Zones.
NODE+ / Installation & Commission Manual / © GFE 220331
28