There is only one I/O timer so once it has expired events activating further delayed I/O groups will cause immediate I/O
operation.
NOTE:
Delays will only occur if the front panel ACTIVE DELAYS button has been set to on. Specific I/O modules (function
5-6) and specific detectors (function 6-1-6) can be set to override this delay.
5-8 Select Disable I/O Group
Allows a specific disablement I/O group to be activated per zone.
5-9 Configure Remote Inputs
Allows the user to configure the remote inputs behaviour REM1 and REM2 Each remote input can be configured with the following
options:
EVACUATION
DISABLE SELECTED DETECTORS
USER ACCESS
RESET
6 Device Set-up
Allows specific settings to be selected for individual Analogue Loop devices.
6-1 General
Settings common to all types of Analogue Loop devices.
6-1-1 Disable Loops
Allows a specific Analogue Loop to be disabled or enabled. The default is enabled.
All devices on the disabled loop will cease to operate with the exception of the (audible) output from loop sounders.
If the loop is disabled it will be indicated when programming mode is exited. It can be reviewed using the DISABLED
(QUEUE REVIEW) button.
6-1-2 Device Disable
Allows a specific device to be disabled or enabled. The default is enabled.
Disabled devices have both inputs and outputs disabled.
This function does not disable the (audible) output from loop sounders.
Any devices that are disabled will also be indicated when programming mode is exited. They can then be reviewed using
the DISABLED (QUEUE REVIEW) button.
6-1-3 Set Selective Disablement
Allows a specific device to be set up for selective disablement.
The device is only disabled when the SELECTED DETECTORS (DISABLEMENTS) button on the front panel is activated.
This function is intended for use when certain detectors regularly need disabling but are not necessarily in the same Zone.
Outside programming mode, any devices that are currently disabled can then be reviewed using the DISABLED (QUEUE
REVIEW) button.
6-1-4 Set Device Reporting Details
Each device can be set to:
FIRE
FAULT
PRE-ALARM
TRANSPARENT
The default is FIRE reporting.
When the device is activated or reaches its alarm threshold, then the event is reported in accordance with this setting.
FAULT - Primarily intended for use with Input modules, it can allow activation of one input to trigger a fault report rather
than a fire.
PRE-ALARM - Sends warning when the level reported from a detector is 10 below the Alarm threshold. Used for early
warning in sensitive applications.
TRANSPARENT Configuration is ONLY applied to Input/Output or Input units. It is not compliant with EN54.
NODE+ / Installation & Commission Manual / © GFE 220331
32