DEFAULT SETTINGS
FINAL CHECK OUT AND TEST
Before giving power to the equipment, the following check outs are required:
1
Check the electrical connections: a wrong connection may damage both the equipment and the installer.
2
Check the correct position of the limit switches.
3
Preset the mechanical stops in opening and closing.
4
Power the equipment.
5
Check that the red LEDs of the normally closed contacts are on and the green LEDs of the normally open
contacts are off.
6
Check that on the lcd do not appear any mismatch between enabling and input status
7
Check that the relative LEDs turn off when limit switches work.
8
Check that the relative LED turns off when the photocells ray is intercepted.
9
Check that the motors are blocked and ready to work with GATE AT HALFWAY POSITION.
10 Remove possible obstacles in the operating area of the gate, then give the command START. At the first
command, the equipment starts opening, then check that the motion direction is correct, otherwise power
the control unit down, invert the wires in the motors clamps, power the control unit up again and give a new
START command.
11 The gate will stop upon the first limit switch. It is necessary a complete movement to activate the regular
working of the decelerations.
• Parameters type A
• A1
2
SWING GATE/OVERHEAD DOOR/BARRIER TYPE
• A2
3
2 MOTORS
• A3
2
STEP STEP WITH STOP LOGIC
• A5
2
AUTOMATIC CLOSING ENABLED (GENERAL AND PEDESTRIAN)
• Parameters type C
• C1
1
FAST CLOSING DISABLED
• C2
2
INTERMITTENT FLASHING LIGHT
• C3
2
PRE-FLASHING ENABLED
• C4
3
DOUBLE READING OF THE LIMIT SWITCH ENABLED
• C5
2
DECELERATIONS DISABLED
• C6
3
LIMIT SWITCH AMPEROMETRIC ENABLED
• C7
2
PHOTOCELL 1 ENABLED
• C8
1
PHOTOCELL 2 DISABLED
• C9
1
SAFETY EDGE DISABLED
• C10
1
HAMMER STROKE DISABLED
• C11
1
FINAL STROKE DISABLED
• C12
1
ADDITIONAL TIME T3 EXCLUDED
• C13
1
HYDRAULIC LOCKING MAINTENANCE EXCLUDED
• C14
2
SOFT START 0,5 s
• Parameters type F
• F1
10
MOTOR 1 FORCE
• F2
05
MOTOR 1 DECELERATION
F3
80
AMPEROMETRIC MOTOR 1 FORCE
F4
50
AMPEROMETRIC MOTOR 1 DECELERATION
F5
10
F6
05
F7
80
F8
50
H
H1
25
MOTOR 1 OPENING TIME
H2
25
MOTOR 1 CLOSING TIME
H3
20
MOTOR 1 DECELERATION TIME
H4
25
MOTOR 2 OPENING TIME
H5
25
MOTOR 2 CLOSING TIME
H6
20
MOTOR 2 DECELERATION TIME
H7
5
LEAF 2 PHASE SHIFT TIME IN OPENING
H8
5
LEAF 1 PHASE SHIFT TIME IN CLOSING
H9
20
PAUSE TIME
H10
5
PEDESTRIAN OPENING TIME
H11
20
PEDESTRIAN PAUSE TIME
®
®
®
®
®
®
®
®
®
®
®
®
®
®
®
®
®
®
®
®
•
®
•
®
•
®
MOTOR 2 FORCE
•
®
MOTOR 2 DECELERATION
•
®
AMPEROMETRIC MOTOR 2 FORCE
•
®
AMPEROMETRIC MOTOR 2 DECELERATION
• Parameters type
•
®
•
®
•
®
•
®
•
®
•
®
•
®
•
®
•
®
•
®
•
®
• Parameters type E
• E1
1
PHOTO 1 TEST DISABLED
E3
1
SAFETY DEVICES TEST DISABLED
E5
1
IN “PEDESTRIAN CLOSING”, ACTIVATES COMPLETE OPENING
E7
1
COURTESY LIGHT WITH 2 MOTORS DISABLED
E9
1
EXTERNAL CLOCK CONTACT DISABLED
E90
0000
NUMBER OF CYCLES
E92
1234
INSTALLER CODE
E94
XX_YY
FIRMWARE RELEASE
E96
0000
NUMBER OF CYCLES DONE
E98
0000g
NUMBER OF OPERATION DAYS
®
•
®
•
®
•
®
•
®
•
®
•
®
•
®
•
®
•
®