INSTALLATION
INSTALLATION WARNINGS
Use cable glands that can assure the correct mechanical connection of the wiring and maintain the IP55
protection degree of the box (2).
• Before the installation, fit a magnetothermal or differential switch with a maximum capacity of 10A upstream of
the system. The switch must guarantee omnipolar separation of the contacts with an opening distance of at
least 3 mm.
• To prevent possible interference, differentiate the power cables and always keep them separate (minimum
cross-section 1.5 mm²) from the signal cables (minimum cross-section 0.5 mm²).
• Make the connections referring to the following tables and to the attached screen-print. Be extremely careful to
connect in series all the devices that are connected to the same N.C. (normally closed) input, and in parallel all
the devices that share the same N.O. (normally open) input. Incorrect installation or improper use of the
product may compromise system safety.
• Keep all the materials contained in the packaging away from children, since they pose a potential risk.
• The manufacturer declines all responsibility for improper functioning of the automated device if the original
components and accessories suitable for the specific application are not used.
• After installation, always check carefully proper functioning of the system and the devices used.
• This instruction manual addresses persons qualified for installation of “live equipment”. Therefore, good
technical knowledge and professional practice in compliance with the regulations in force are required.
• Maintenance must be carried out by qualified personnel.
• Before carrying out any cleaning or maintenance operation, disconnect the control unit from the mains.
• This control unit may only be used for the purpose for which it was designed. Check the aim of the final use
and make sure that all safety measures are taken.
• Use of the product for purposes different from the intended use has not been tested by the manufacturer,
therefore any work is carried out on full responsibility of the installer.
• Mark the automated device with visible warning plates.
• Warn the user that children or animals may not play or stand around near the gate.
• Appropriately protect the danger points (for example, using a sensitive frame).
• The control board alone will not ensure safety against crushing. Make sure that the safety devices connected
to the control board are appropriate for the purpose.
• Possibility to program: automatic closing, fast closing, pre-flashing, hammer stroke, final closing and opening
stroke, courtesy light, ending movement additional time, flashing light (both flashing and fixed), external watch
management with three different modalities, number of cycles for scheduled maintenance, installer code and
number of performed cycles and power supply days.
WARNINGS FOR THE USER
In the event of an operating fault or failure, cut the power upstream of the control unit and call Technical Service.
Periodically check functioning of the safety devices. Any repairs must be carried out by specialised personnel
using original and certified materials.
The appliance is not to be used by children or people with reduced physical, sensory or mental capabilities, or
lack of experience and knowledge, unless they have been given supervision or instruction.
Do not touch the control unit for adjustments and/or maintenance.
WARNING: IMPORTANT SAFETY INSTRUCTIONS
It is very important to follow the present instructions for your own safety.
Please keep this manual.
ELECTRICAL CONNECTIONS: FASTONS
Cable colour
RED
Terminal
CF1
CF2
Description
Secondary connection of 24Vac transformer
ELECTRICAL CONNECTIONS: TERMINAL BOARDS
Description
JP1
Terminal
Battery charger equipment connection
Motor 1
1
5
Position
Signal
AC
M1
Battery charger equipment connection
Motor 1
2
6
AC
M1
Battery charger equipment connection
Motor 2
3
7
+ SK
M2
4
8
- SK
M2
Battery charger equipment connection
Motor 2
9
10
LAMP
LAMP
Flashing light output 24Vdc 10W max.
Flashing light output 24Vdc 10W max.
Working
:
Fast flashing in opening,
off in stand-by,
fast flashing in closing
JP4
11
12
13
14
16
17
COM
EL1
EL2
COM
+ ACC
+ SAF
Negative electrical lock (common)
Po24 Vdc motor 1 electrical lock
Po24 Vdc motor 2 electrical lock
External accessory power supply negative (common)
+24Vdc external accessory power supply (photocells, radio, etc.)
+24Vdc external safety device power supply
15
WARNING
LIGHT
Warning light output 24Vdc 3W max.
Working
:
Slow flashing during opening,
fixed light during pause,
fast flashing during closing