6.1.3. Vibration Channels
Picture 14: configuration menu vibration channels
On the configuration site Vibration Channels, the individual analogue inputs can be configured.
Via the button Vibration Channels
→
New a new sensor can be added and afterwards be
configured in the table. The following parameters are available:
•
Name:
an arbitrary name for the sensor description or name of the measurement position.
•
Channel:
the corresponding input channel
•
Reference Speed:
the speed that is used for the order spectra of this sensor
•
Sensitivity / V:
the sensitivity of the sensor. If a calibration file is given on the general site,
the value from the calibration file is used automatically.
•
Offset:
the offset of the sensor. For accelerometers with IEPE interface this value is usually
0. For analogues displacement sensors, the offset of the displacement sensor must be
entered.
•
Unit:
the physical unit of the sensor
•
Measurement range
: the measurement range of the channel. Here you can select from
10 V to
1 V.
•
Measurement time
: the measurement time is changed for all channels accordingly. It can
be chosen from a pool of 8 measurement times. Alternatively, the measurement time can
be set to undefined. In this case the measurement must be stopped explicitly to finish the
measurement.
•
Sampling frequency:
The sampling frequency can be set individually for each channel from
a pool of 9 sampling frequencies.
•
Coupling:
The coupling can be chosen for each channel individually from IEPE, AC or DC.
If the configuration type balancing was chosen, a balancing layer must be assigned to each
sensor. Furthermore, the sampling frequency is fixed to 51.2 kHz for all sensors.