9900-1BC Batch Controller Manual
Advanced Mode
(See Input Menu - Page 19)
EOB PULS – End of Batch Pulse:
Generates a pulse at the end of a batch which can
be used for external counter or to start a second
batch controller.
HI FLOW – High Flow:
In HI FLOW Mode, Relay is energized at Set Flow
value and will be de-energized at Set Flow value
minus Hysteresis value.
If STOP BATCH is set to YES, the hysteresis is
ignored. A batch stopped for a high flow condition
will not automatically resume when the flow
decreases below the hysteresis level.
User interaction is required to resume the batch.
OVERRUN – Overrun:
Activates relay when Overrun reaches the specified
volume (see Set Overrun Volume, page 21).
Note:
The Overrun Alarm Volume must be greater
than the Manual Compensation Volume. If the
Overrun Alarm Volume is less than or equal to the
Manual Compensation Volume, the Overrun Alarm
will activate on every batch.
SRC VOL – Source Volume:
Activates relay when Source Volume falls to specified
volume (
only available when "Source Volume" is ON)
0%
0%
100%
0%
100%
0%
100%
Overrun
90% 100%
Relay 2 Bypass
Relay 1 Main
Time
0%
Flow Input
X
Time
Time
Time
Time
Hysteresis
Time
Process
Hysteresis
Time
Low Setpoint
Process
Time
High Limit
Hysteresis
Low Limit
Process
High
Setpoint
Relay energized
Relay de-energized
% Batch Percentage
Window
Time
High Limit
Hysteresis
Low Limit
Process
Window
Hysteresis
0%
0%
100%
0%
100%
0%
100%
Overrun
90% 100%
Relay 2 Bypass
Relay 1 Main
Time
0%
Flow Input
X
Time
Time
Time
Time
Hysteresis
Time
Process
Hysteresis
Time
Low Setpoint
Process
Time
High Limit
Hysteresis
Low Limit
Process
High
Setpoint
Relay energized
Relay de-energized
% Batch Percentage
Window
Time
High Limit
Hysteresis
Low Limit
Process
Window
Hysteresis
0%
0%
100%
0%
100%
0%
100%
Overrun
90% 100%
Relay 2 Bypass
Relay 1 Main
Time
0%
Flow Input
X
Time
Time
Time
Time
Hysteresis
Time
Process
Hysteresis
Time
Low Setpoint
Process
Time
High Limit
Hysteresis
Low Limit
Process
High
Setpoint
Relay energized
Relay de-energized
% Batch Percentage
Window
Time
High Limit
Hysteresis
Low Limit
Process
Window
Hysteresis
Hysteresis
Time
Process
Hysteresis
Time
Low Setpoint
Process
Time
High Limit
Hysteresis
Low Limit
Process
High
Setpoint
Relay energized
Relay de-energized
% Batch Percentage
Window
Time
High Limit
Hysteresis
Low Limit
Process
Window
Hysteresis
Hysteresis
Time
Process
Hysteresis
Time
Low Setpoint
Process
Time
High Limit
Hysteresis
Low Limit
Process
High
Setpoint
Relay energized
Relay de-energized
% Batch Percentage
Window
Time
High Limit
Hysteresis
Low Limit
Process
Window
Hysteresis
Relay Mode Settings