9900-1BC Batch Controller Manual
RELAY MULTIPLE Mode options (see discussion on page 13)
Missing Signal On/Off
Energizes selected relay if signal is missing. Select ON or OFF.
Overrun On/Off
Energizes selected relay if overrun occurs. Select ON or OFF.
Hi Flow On/Off
Energizes selected relay if Hi Flow condition occurs. Select ON or OFF.
Error On/Off
Energizes selected relay if an error condition occurs. Select ON or OFF.
RELAY TWO STAGE Mode option (see discussion on page 13)
Main Relay Select
(ADVANCED Mode only) Selects the specified relay as the main relay for two-stage
valve control. This relay will be de-energized when the batch volume reaches the setpoint percentage.
Setpoint Percent Select
Selects the percentage of batch volume at which the main relay will be
de-energized. Default = 95.0%.
Bypass Relay Select
Selects the specified relay as the Bypass relay for two-stage valve control.
This relay will remain energized while the batch is running.
Relay Bypassed
The specified relay is in Bypass.
Note:
A relay is taken out of bypass using the Bypass select screen, found under the relay which is in
TWO STG Mode.