6
9900-1BC Batch Controller Manual
Proper operation of the batch module requires Generation II, version 25-04 software in the 9900
Transmitter. To determine the software version of the 9900 Transmitter, please see instructions
below.
If your unit has an older version of software, please contact your local GF sales office for
upgrade instructions.
Instructions for determining the version of the 9900:
1.
Press and Hold the Enter key until the ENTER
MENU screen is displayed.
2.
Press the Up arrow key once, the
OPTION item should be blinking.
3.
Press the Enter key to navigate to the Option
screen.
4.
Simultaneously press and hold all four buttons
(Up, Down, Right Arrows and Enter)
5.
The screen will change and show
“SW VER 25 – 04”
6.
If the software version is less than
25-04, please contact your local GF sales office
for upgrade information.
ENTER
3s
1x
HOLD
ENTER
ENTER
WARNING!
Georg Fischer Signet strongly recommends against the use of 4 to 20 mA current loop controlled
devices, such as actuated valves, for use as Batch control elements. On power up, the 9900
current loop will supply a 12 mA signal on the current loop output while the system initializes, if an
error occurs, such as a missing Digital (S
3
L) sensor or overrun, the current loop will go to the error
current of 3.6 or 22 mA. Improper programming of the loop completion current or the loop error
current can cause unintended actuation of the current loop controlled device. These can cause an
unexpected discharge of material from the batch system.
Software
Important
Note:
The 9900 in Batch mode does not support the 3-9900.270-MX Modbus or the 3-9900.395 HART Communication modules.
No data is available from the 9900 when configured for Batch operation.