background image

6

Signet 8150 Flow Totalizer

     RED

#1 

#2 

Totalizer 1

Remote reset 

Connect shield

to Ground wire

Splice BLK and SHLD

together outside of terminal

BLACK 

SHIE

LD

 

515

525

Battery Installation and Replacement

Wiring

The wiring is identical for the panel mount and the field mount 

versions of the Totalizer.

• 

Only one wire should be inserted into a terminal. Splice 

double wires outside the terminal.

• 

External Reset for Total #1:

 Use no more than  

30 m (100 ft) of 2-conductor twisted-pair cable connected 

to a dry contact (for example, an ordinary door-bell button 

or relay contact).

• 

Only Totalizer #1 can be reset by the external connection.

• 

Total #1 will not be displayed unless it is the standard 

totalizer selection. 

Instructions

1.  Remove 10 mm (

3

/

8

 in.) of insulation from  

sensor cable conductors.

2.  Press down on orange lever to open terminal.

3.  Insert wire into terminal until it hits bottom.

4.  Release the lever to secure wire.

10 mm 

Input Wiring

Use this wiring scheme for Signet models 515 and 525.

Terminal Function

 

Signal Ground

 

Sensor signal

 

Open Collector Signal

 

DC Power to sensor

 

Ground

 

Ext. Reset

Two 

3.6 V lithium thionyl chloride 

batteries, AA-size

(7400-0011) are installed in the Totalizer.

NOTE:

   The 8150 will not operate with standard 1.5 V  

alkaline batteries.  USE 3.6 V SAFT LS14500 

LITHIUM BATTERIES OR EQUIVALENT ONLY!

CAUTION 

When replacing batteries, 

remove and replace 

one battery at a time 

Remove and replace 

this battery first. 

Note:  Lithium Batteries 

Dispose of properly! 

Replace with 3.6 V Lithium battery 

+  + 

1.  Remove pull tabs from the batteries to power up the 8150.

2.  Note: 

Observe polarity!

 Both batteries should face the 

same direction.

3.  When the “low battery” indicator appears on the display, 

both batteries should be replaced within 90 days.

4.  Remove and replace battery #1 first, then remove and 

replace battery #2.  This ensures that all settings and 

totalizer values are saved.

5.  If the low battery symbol reappears for more than 10 

seconds after installing new batteries, one battery is 

reversed, or battery #2 was installed before battery #1.

6.  Secure the batteries by fastening the  

hook-and-loop straps.

DISPOSE OF EXPENDED BATTERIES 

PROPERLY!

  Lithium batteries contain 

hazardous chemicals.

Dispose of batteries in accordance with 

local regulation.

Shipping Notice:

If the battery pull tabs have been removed, remove the 

batteries from the totalizer prior to shipping.

Содержание Signet 8150

Страница 1: ...150 Flow Totalizer is a battery powered instrument capable of providing uninterrupted flow and total volume information for 4 years and beyond The unique features of the 8150 include Easy setup and di...

Страница 2: ...mical poisoning dry out or mishandling e g broken glass damaged membrane freezing and or extreme temperatures Thank you for purchasing the Signet line of Georg Fischer measurement products If you woul...

Страница 3: ...umidity 0 to 95 non condensing Rating NEMA 4X IP65 front panel Shipping Weight 0 5 kg 1 1 lbs Quality Standards CE CUL UL Manufactured under ISO 9001 for Quality ISO 14001 for Environmental Management...

Страница 4: ...ng it so the square tab is close to the conduit ports 3 Insert the mounting screw into the conduit base so the head of the screw presses down on the locking ring when tightened 4 Connect sensor wires...

Страница 5: ...ied in bold type are required for the installation Other parts are shown for reference only Use 2 conductor shielded cable no more than 30 m 100 ft long Remote Field mount on Pipe Flow Totalizer 3 815...

Страница 6: ...d 6 Ext Reset Two 3 6 V lithium thionyl chloride batteries AA size 7400 0011 are installed in the Totalizer NOTE The 8150 will not operate with standard 1 5 V alkaline batteries USE 3 6 V SAFT LS14500...

Страница 7: ...uring normal operation Illustrated No flow for 3 hours Operation Standard Menu Settings ENTER 5 sec Function Factory set Description AUTO CALIBRATION No setting See page 11 for detailed information FL...

Страница 8: ...lement to the last digit 6 Press the key one time to scroll the flashing digit to 1 7 Press the ENTER key to complete the edit process 8 Press the and keys together to exit the Calibrate menu store th...

Страница 9: ...rge volume Total 2 tot2 can be reset only by entering the security code in the calibration menu Total 2 is identified by a flashing display every six seconds Application Use Total 2 for extended measu...

Страница 10: ...lizer value will begin flashing The totalizer will automatically reset to 00000000 in 8 seconds While the display is flashing you can cancel the reset by pressing and keys together 5 Press and keys to...

Страница 11: ...ted K Factor is less than 0 001 or greater than 999999 Verify the flow rate and start the AutoCAL procedure from step 1 8 Press and keys together to store the new value in the memory The display will...

Страница 12: ...o the decimal point 5 Press the key one time to move the decimal point one position to the right 6 Press the ENTER key to return to the menu 7 Press and keys together to exit the menu and return to no...

Страница 13: ...ay will not auto range If the decimal is set to tenths the flow rate display will show tenths up to 999 9 then the auto range will switch to whole numbers 1000 to 9999 If the decimal is set to hundred...

Страница 14: ...bilized but a sharp change in flow rate is not represented for 60 seconds or longer dotted green line With SPEED at 60 seconds and SENSITIVITY set to 6 the flow rate is stabilized while the sudden shi...

Страница 15: ...ss the ENTER key to return to the menu 6 Press and keys together to exit the menu and return to normal operation The display shows Storing for a few seconds then returns to the normal operating displa...

Страница 16: ...4 IR4T012 62 979 16 639 1 1 2 IR4T015 46 688 12 335 2 IR4T020 29 459 7 7832 BRONZE TEES ON SCH 40 PIPE 1 BR4T010 104 54 27 619 1 1 4 BR4T012 62 979 16 639 1 1 2 BR4T015 46 688 12 335 2 BR4T020 29 459...

Страница 17: ...950 DN 40 SFMT015 43 490 11 490 DN 50 SFMT020 25 908 6 8450 DN 65 SFMT025 18 067 4 7732 DN 80 SFMT030 12 357 3 2648 DN 100 SFMT040 8 0599 2 1294 DN 125 SFMT050 4 4312 1 1707 DN 150 SFMT060 3 2271 0 8...

Страница 18: ...ceiving a signal from the flow sensor 1 There is no flow in the pipe 2 Flow sensor is not turning due to blockage or damage 3 Sensor wiring is loose or incorrect In AutoCal the calculated K Factor is...

Страница 19: ...19 Signet 8150 Flow Totalizer Notes...

Страница 20: ...roof rear cover for panel mount totalizer 3 9000 392 159 000 368 Liquid tight connector kit includes 3 connectors 3 9000 392 1 159 000 839 Liquid tight connector NPT 1 connector 3 9000 392 2 159 000 8...

Отзывы: