18

Signet 8150 Flow Totalizer

Troubleshooting

Display Condition

Probable Cause

Suggested Solutions

Batteries are dead or missing.

Replace both batteries.

Pull tabs have not been removed.

Remove plastic pull tabs protecting the batteries.

The flow rate is greater than “9999”.

1.  Reduce the flow rate.

2.  Change the Timebase to a smaller value.

  (Example: Change from “Day” to “Hour”)

3.  Change the flow units to a larger measure.

  (Example: Change from “Liters” to “Gallons”)

 

NOTE:

 If the Flow K-Factor is changed, be 

sure to make a corresponding change to the 

TOTAL K-Factor.

8150 is not receiving a signal from the flow sensor.

1.  There is no flow in the pipe.

2.  Flow sensor is not turning due to blockage 

or damage.

3.  Sensor wiring is loose or incorrect.

In AutoCal, the calculated K-Factor is outside the 

range of the 8150 (less than 0.001 or greater than 

99999).

Press ► key to start AutoCAL procedure again.

Make sure that the flow rate entered is accurate.

The flow rate display is 

erratic and non-linear

Usually caused by inadequate straight pipe run 

upstream of sensor.

1.  Correct piping layout to provide more straight 

pipe upstream of sensor.

2.  Set the SPEED to higher setting to average out 

the fluctuations caused by piping conditions 

(see Speed, section 14).

Both batteries are too depleted to safely store 

settings.

Replace battery #1, then replace battery #2.

Содержание Signet 8150

Страница 1: ...150 Flow Totalizer is a battery powered instrument capable of providing uninterrupted flow and total volume information for 4 years and beyond The unique features of the 8150 include Easy setup and di...

Страница 2: ...mical poisoning dry out or mishandling e g broken glass damaged membrane freezing and or extreme temperatures Thank you for purchasing the Signet line of Georg Fischer measurement products If you woul...

Страница 3: ...umidity 0 to 95 non condensing Rating NEMA 4X IP65 front panel Shipping Weight 0 5 kg 1 1 lbs Quality Standards CE CUL UL Manufactured under ISO 9001 for Quality ISO 14001 for Environmental Management...

Страница 4: ...ng it so the square tab is close to the conduit ports 3 Insert the mounting screw into the conduit base so the head of the screw presses down on the locking ring when tightened 4 Connect sensor wires...

Страница 5: ...ied in bold type are required for the installation Other parts are shown for reference only Use 2 conductor shielded cable no more than 30 m 100 ft long Remote Field mount on Pipe Flow Totalizer 3 815...

Страница 6: ...d 6 Ext Reset Two 3 6 V lithium thionyl chloride batteries AA size 7400 0011 are installed in the Totalizer NOTE The 8150 will not operate with standard 1 5 V alkaline batteries USE 3 6 V SAFT LS14500...

Страница 7: ...uring normal operation Illustrated No flow for 3 hours Operation Standard Menu Settings ENTER 5 sec Function Factory set Description AUTO CALIBRATION No setting See page 11 for detailed information FL...

Страница 8: ...lement to the last digit 6 Press the key one time to scroll the flashing digit to 1 7 Press the ENTER key to complete the edit process 8 Press the and keys together to exit the Calibrate menu store th...

Страница 9: ...rge volume Total 2 tot2 can be reset only by entering the security code in the calibration menu Total 2 is identified by a flashing display every six seconds Application Use Total 2 for extended measu...

Страница 10: ...lizer value will begin flashing The totalizer will automatically reset to 00000000 in 8 seconds While the display is flashing you can cancel the reset by pressing and keys together 5 Press and keys to...

Страница 11: ...ted K Factor is less than 0 001 or greater than 999999 Verify the flow rate and start the AutoCAL procedure from step 1 8 Press and keys together to store the new value in the memory The display will...

Страница 12: ...o the decimal point 5 Press the key one time to move the decimal point one position to the right 6 Press the ENTER key to return to the menu 7 Press and keys together to exit the menu and return to no...

Страница 13: ...ay will not auto range If the decimal is set to tenths the flow rate display will show tenths up to 999 9 then the auto range will switch to whole numbers 1000 to 9999 If the decimal is set to hundred...

Страница 14: ...bilized but a sharp change in flow rate is not represented for 60 seconds or longer dotted green line With SPEED at 60 seconds and SENSITIVITY set to 6 the flow rate is stabilized while the sudden shi...

Страница 15: ...ss the ENTER key to return to the menu 6 Press and keys together to exit the menu and return to normal operation The display shows Storing for a few seconds then returns to the normal operating displa...

Страница 16: ...4 IR4T012 62 979 16 639 1 1 2 IR4T015 46 688 12 335 2 IR4T020 29 459 7 7832 BRONZE TEES ON SCH 40 PIPE 1 BR4T010 104 54 27 619 1 1 4 BR4T012 62 979 16 639 1 1 2 BR4T015 46 688 12 335 2 BR4T020 29 459...

Страница 17: ...950 DN 40 SFMT015 43 490 11 490 DN 50 SFMT020 25 908 6 8450 DN 65 SFMT025 18 067 4 7732 DN 80 SFMT030 12 357 3 2648 DN 100 SFMT040 8 0599 2 1294 DN 125 SFMT050 4 4312 1 1707 DN 150 SFMT060 3 2271 0 8...

Страница 18: ...ceiving a signal from the flow sensor 1 There is no flow in the pipe 2 Flow sensor is not turning due to blockage or damage 3 Sensor wiring is loose or incorrect In AutoCal the calculated K Factor is...

Страница 19: ...19 Signet 8150 Flow Totalizer Notes...

Страница 20: ...roof rear cover for panel mount totalizer 3 9000 392 159 000 368 Liquid tight connector kit includes 3 connectors 3 9000 392 1 159 000 839 Liquid tight connector NPT 1 connector 3 9000 392 2 159 000 8...

Отзывы: