background image

7

Signet 5500 Flow Monitor

9.3 OPTIONS 

Menu

Choose: 

 

Change: 

Save: 

quick  

press 

To return to  
VIEW menu: 

quick  

press 

To restore original value: 

Display contrast 

Low   --   --   --   --   --   High 

4 mA adjust 

Loop output 

Loop output 

20 mA adjust 

Flow display 

Decimal 

Press 

 

     

 

     

will appear during code entry.

keys in sequence to enter menu,   

Total display 

Total decimal 

Display averaging 

4s 

8s 

0s 

Loop output 

4 mA setpoint 

20 mA setpoint 

Loop output 

J↓ 

A↑ 

ENTER 

"SAVING" 

briefly 

displays 

Totalalizer reset 

VIEW menu= 

VIEW menu= 

A. 

B. 

C. 

D. 

E. 

F. 

G. 

H. 

I. 

J. 

Auxiliary out logic 

Active Low or High

Menu Settings A - J: 

(Factory default displays shown)

A.  Selects LCD display contrast: 5 levels

B. Selects 

fl

 ow display decimal: 

 

*****. to ** . ***

C.  Selects totalizer display decimal: 
 

********. to ****** . **

D.  Selects LCD display averaging: 
 

Off = 0 seconds, Low= 4 seconds, High= 8 
seconds (also affects 4 to 20 mA output)

E.  Sets 4 mA output setpoint. 4 mA and 20 mA 

setpoints are reversible.

F.  Sets 20 mA output setpoint. 20 mA and 4 mA 

setpoints are reversible.

G.  Sets 4 mA current output: 3.0 to 5.0 mA 

(overrides 4.00 mA factory calibration)

H.  Sets 20 mA current output: 19 to 21 mA 

(overrides 20.00 mA factory calibration)

I.  Selects totalizer reset options: Lock "Off" 

disables the VIEW menu access code 
feature; Lock "On" enables the feature (sec. 
9.1 A). When enabled, the operator must 
enter an access code for totalizer reset 
privileges. The totalizer will be reset in either 
case if a contact closure is detected at rear 
reset terminals (sec. 5).

J.  Selects Auxiliary output logic: 

•  Active Low logic (factory default): Output 

changes from high to low when active, see 
diagram below.

•  Active high logic: Output changes from low 

to high when active, see diagram below.

Inactive (Off) 

Active Low Logic (factory default) 

Active (On) 

Inactive (Off) 

Active High Logic

Active (On)

Содержание Signet 5500

Страница 1: ...Double Insulated DC or AC power Contents 1 Power Connections 2 Compatible Sensor Wiring 3 Sensor Pulse Output Connections 4 Auxiliary Pulse Output Connections 5 Totalizer Reset Connections 6 4 20 mA...

Страница 2: ...t PNP source input 5500 Terminals External power supply 28 VDC max Other instrument Gnd Input NPN sink input Gnd AUX output N 5500 Terminals Signal output Signal ground 3 28 VDC External power supply...

Страница 3: ...wer is applied after the relay 2 setpoint is reached 6 4 to 20 mA Current Output Connections sec 8 4 4 20 mA 5500 Terminals 4 20 mA Fuse 1 8A Technical Notes 1 8 A fuse recommended customer supplied 4...

Страница 4: ...nsor also displayed on totalizer To enable the totalizer function the operator must set the relay or auxiliary pulse volume setpoint to 1 0000 sec 9 2 H 9 2 L Totalizer function ideal for external cou...

Страница 5: ...djustments ENTER OPTIONS sec 9 3 CALIBRATE sec 9 2 VIEW sec 9 1 2 seconds 5 seconds Press hold ENTER key for menu access Menu Displays A H Factory default displays shown A Flowrate and resettable tota...

Страница 6: ...disable hysteresis feature L Sets auxiliary output pulse volume setpoint 0 0001 99999 sec 8 2 Set to 1 0000 factory default to enable totalizer function sec 8 2 M Sets auxiliary output pulse width 0...

Страница 7: ...nds High 8 seconds also affects 4 to 20 mA output E Sets 4 mA output setpoint 4 mA and 20 mA setpoints are reversible F Sets 20 mA output setpoint 20 mA and 4 mA setpoints are reversible G Sets 4 mA c...

Страница 8: ...ilicone rubber Weight Approximately 500 g 18 oz Display Type Microprocessor controlled air core meter movement and backlit alphanumeric 2 x 16 LCD Update rate Flow 1s totalizer 200 ms Contrast User se...

Страница 9: ...96 mm 3 8 in RELAY 2 RELAY 1 ENTER 4 0 1 2 3 5 6 7 8 9 10 GPM Signet Monitor 92 x 92 mm 3 62 x 3 62 in Panel cutout Menu Parameters Display Description Range Factory Default A Flow rate and units Rese...

Страница 10: ...max _Gallons E Total K Factor 0 0001 99999 60 000 F Relay 1 mode Relay 1 setpoint Low or High 0 0000 99999 Pulse 0 0001 99999 Low 10 000 GPM G Relay 1 Hysteresis Hysteresis volume 0 0000 99999 2 0000...

Страница 11: ...l to D Display averaging Off 0 sec Low 4 sec High 8 sec Off E 4 mA setpoint Unlimited 0 0000 GPM F 20 mA setpoint Unlimited 100 00 GPM G 4 mA adjust 3 0 to 5 0 mA 4 00 mA H 20 mA adjust 19 to 21 mA 20...

Страница 12: ...mall Reduce auxiliary output pulse width setting sec 9 2 M or increase pulse volume setting sec 9 2 L Must be between 0 0001 99999 Relay 1 Relay 2 or Auxiliary output AUX pulse volume setpoint must be...

Отзывы: