Signet 5500 Flow Monitor

Electrical

Power:  
•  12 to 24 VDC or 12 to 24 VAC, unregulated, 50-60 Hz, 10 W max.

Relay contacts (2 sets): 
  • Mechanical SPDT contacts
  • Max voltage rating: 

5 A @ 30 VDC,

 

5 A @ 125 VAC, or

 

3 A @ 250 VAC, (power factor  = 1.0)

  • Hysteresis: User adjustable

Current output:  4 to 20 mA, non-isolated, internally powered, 

fully adjustable and reversible 

Update rate: 

100 ms

Max loop
 impedance:  350 

Ω

 max with a 12 V instrument supply 

voltage, 950 

Ω

 max with a 24 V instrument 

supply voltage

Accuracy: 

±0.1% of max range

Sensor (PLS) Auxiliary (AUX) pulse outputs:
•  Open-collector transistor, optically isolated, 5 mA max. sink,

28 VDC max. pull-up voltage, programmable (AUX) pulse width 

Totalizer reset: 

Front keypad or external contact closure,
30 m (100 ft) max cable length

•  External contact closure overrides security feature (sec. 5)

General

Sensor
 compatibility:  All 

Signet 

fl

 ow sensors

Accuracy: 

±0.5% of reading

Input: Optically 

isolated

Enclosure:
•  Rating: 

NEMA 4X/IP65 front

•  Dimensions: 

1/4 DIN, 96 x 96 x 88 mm (3.8 x 3.8 x 3.5 in.)

•  Case material:  ABS plastic
•  Keypad: 

Sealed 4-key silicone rubber

•  Weight: 

Approximately 500 g (18 oz.)

Display:
•  Type: 

Microprocessor controlled air-core meter 
movement and backlit alphanumeric 2 x 16 LCD

•  Update rate: 

Flow = 1s, totalizer = < 200 ms

•  Contrast: 

User selected, 5 levels

• Annunciators:  2 LEDs

Totalizers:
  • 8-digit resettable with security option
  • 8-digit non-resettable

Environmental

Operating temp.:  -10 to 55 °C (14 to 131 °F),

50 °C (122 °F) max. with optional rear cover

Storage temp.: 

-15 to 80 °C (5 to 176°F)

Rel. humidity: 

0 to 95%, non-condensing

Altitude: 

4000 m max.

Pollution degree:  2

Noise immunity:  EN50082-2
Noise emissions:  EN55011
Safety: EN61010-1
Agency Approvals
•  CE, UL, CUL
•  Manufactured under ISO 9001 for Quality and
  ISO 14001 for Environmental Management.

•  Power supply, 115 VAC - 24 VAC, #3-5000.075
•  Front snap-on bezel, #3-5000.525 (code 198 840 226)
• Assorted 

fl

 ow unit/multiplier decals, #3-5500.611 (code 198 840 230)

•  5500 instruction sheet #3-5500.090-1 (code 198 869 914)

10. Parts and Accessories

Optional surface mount bracket 

#3-5000.598 (code 198 840 225)

Splashproof rear cover

#3-5000.395 (code 198 840 227)

5 x 5 inch adapter plate for Signet retro

fi

 t

 #3-5000.399 (code 198 840 224)

Internal  
PLS/AUX 
circuits 

GND 

5500 rear PLS/AUX

output terminals

100Ω

11. Specifi cations

China RoHS (Go to www.gfsignet.com for details)

Содержание Signet 5500

Страница 1: ...Double Insulated DC or AC power Contents 1 Power Connections 2 Compatible Sensor Wiring 3 Sensor Pulse Output Connections 4 Auxiliary Pulse Output Connections 5 Totalizer Reset Connections 6 4 20 mA...

Страница 2: ...t PNP source input 5500 Terminals External power supply 28 VDC max Other instrument Gnd Input NPN sink input Gnd AUX output N 5500 Terminals Signal output Signal ground 3 28 VDC External power supply...

Страница 3: ...wer is applied after the relay 2 setpoint is reached 6 4 to 20 mA Current Output Connections sec 8 4 4 20 mA 5500 Terminals 4 20 mA Fuse 1 8A Technical Notes 1 8 A fuse recommended customer supplied 4...

Страница 4: ...nsor also displayed on totalizer To enable the totalizer function the operator must set the relay or auxiliary pulse volume setpoint to 1 0000 sec 9 2 H 9 2 L Totalizer function ideal for external cou...

Страница 5: ...djustments ENTER OPTIONS sec 9 3 CALIBRATE sec 9 2 VIEW sec 9 1 2 seconds 5 seconds Press hold ENTER key for menu access Menu Displays A H Factory default displays shown A Flowrate and resettable tota...

Страница 6: ...disable hysteresis feature L Sets auxiliary output pulse volume setpoint 0 0001 99999 sec 8 2 Set to 1 0000 factory default to enable totalizer function sec 8 2 M Sets auxiliary output pulse width 0...

Страница 7: ...nds High 8 seconds also affects 4 to 20 mA output E Sets 4 mA output setpoint 4 mA and 20 mA setpoints are reversible F Sets 20 mA output setpoint 20 mA and 4 mA setpoints are reversible G Sets 4 mA c...

Страница 8: ...ilicone rubber Weight Approximately 500 g 18 oz Display Type Microprocessor controlled air core meter movement and backlit alphanumeric 2 x 16 LCD Update rate Flow 1s totalizer 200 ms Contrast User se...

Страница 9: ...96 mm 3 8 in RELAY 2 RELAY 1 ENTER 4 0 1 2 3 5 6 7 8 9 10 GPM Signet Monitor 92 x 92 mm 3 62 x 3 62 in Panel cutout Menu Parameters Display Description Range Factory Default A Flow rate and units Rese...

Страница 10: ...max _Gallons E Total K Factor 0 0001 99999 60 000 F Relay 1 mode Relay 1 setpoint Low or High 0 0000 99999 Pulse 0 0001 99999 Low 10 000 GPM G Relay 1 Hysteresis Hysteresis volume 0 0000 99999 2 0000...

Страница 11: ...l to D Display averaging Off 0 sec Low 4 sec High 8 sec Off E 4 mA setpoint Unlimited 0 0000 GPM F 20 mA setpoint Unlimited 100 00 GPM G 4 mA adjust 3 0 to 5 0 mA 4 00 mA H 20 mA adjust 19 to 21 mA 20...

Страница 12: ...mall Reduce auxiliary output pulse width setting sec 9 2 M or increase pulse volume setting sec 9 2 L Must be between 0 0001 99999 Relay 1 Relay 2 or Auxiliary output AUX pulse volume setpoint must be...

Отзывы: